1
Service
Service Manual
20
3-Way Valve Time
The optional Lochinvar Multi-Temperature Loop Control
Board (MTLCB) can be used to control the supply temperature
up to three (3) sub-loops, corresponding to each of the three
(3) SH set points, through the use of 3-way mixing valves. To
ensure the MTLCB will control these temperature properly,
it is necessary to let the control know how much time these
mixing valves require to fully open and close. Program
this time into the
3-Way Valve Time
parameter. Since this
parameter applies to all of the mixing valves used, the actual
open/close time must be approximately the same for each
one. The minimum setting is 1 second, and the maximum
setting is 255 seconds. The default setting is 20 seconds.
Data Logging
Reset log errors
The reset log errors function clears the last 10 errors log.
Functions
Service Mode Delay
By pressing the pin button on the front of the display for
five (5) seconds, the control will be placed in Service Mode.
This will override all other heat demands. The Service Mode
allows the installer to set the unit to any firing rate for the
purpose of combustion analysis. The delay sets the length of
time the boiler will stay in the Service Mode if no keys have
been pressed before going back to its original state. This
parameter can only be changed by the installer by accessing
the
Service Mode Delay parameter
. The time range of this
parameter is 1 to 10 minutes. The default value is 10 minutes.
Freeze Protection Pump On
The SMART SYSTEM control will turn on the boiler and
system pump outputs whenever the inlet temperature drops
below this setting. This is done to prevent the water in the
heat exchanger from freezing. Certain low-temperature
applications (such as snow melt) can operate at temperatures
around freezing, so this setting needs to be lowered in these
cases. The installer can adjust the temperature at which the
pump outputs are turned on by accessing
Freeze Protection
Pump On parameter
. The minimum setting is -3°F (-19°C),
and the maximum setting is 45°F (7.2°C). The default setting
is 45°F (7.2°C).
Freeze Protection Burner On
If running the pumps does not prevent the inlet temperature
from falling closer to freezing, the SMART SYSTEM control
will fire the burner at low fire. The installer can adjust the
temperature at which the burner fires by adjusting the F
reeze
Protection Burner On parameter
. The minimum setting is
-3°F (-19°C), and the maximum setting is 45°F (7.2°C). The
default setting is 37°F (2.8°C).
To save any changes and return to the Home Screen, press
the RIGHT SELECT [HOME] key. To return to the Status
Screen without saving the changes, press the LEFT SELECT
[EXIT] key.
Display Timeout
This is the time in which the display remains illuminated.
The range is 10 seconds to 10 minutes. The default is 3
minutes.
Temperature Settings
Space Heating (SH1, SH2, SH3) Set Point
There are three (3) individual user set points for better zone
control. These are listed as SH1 Set Point through SH3 Set
Point. If multiple set points are calling for heat the highest set
point has priority. The range is
SH Minimum Set point
to
SH
Maximum Set point
. The default is 125°F (52°C).
Space Heating (SH) Minimum Set Point
The SH minimum set point sets the minimum water
temperature set point that can be used for space heating
operation. The user or installer will not be able to program
the control with a lower SH set point. This parameter can
only be changed by the installer by accessing
Minimum SH
Set point parameter
. The temperature range of this parameter
is 32°F (0°C) to the space heating maximum set point. The
default value is 32°F (21°C).
Space Heating (SH) Maximum Set Point
The SH maximum set point sets the maximum water
temperature set point that can be used for space heating. The
user or installer will not be able to program the control with a
higher SH set point. This parameter can only be changed by
the installer by accessing
Maximum SH Set point parameter
.
The temperature range of this parameter is the space heating
minimum set point to 180°F (82°C). The default value is
180°F (82°C).
SH1 - SH3 Offset Set Point
The SH offset sets how many degrees above set point the
temperature has to go before the boiler will shut off. This
parameter can only be changed by the installer by accessing
parameters
SH1, 2 and 3 Offset Set point parameters
. The
temperature range of these parameters is 0°F to 20°F. The
default value is 10°F.
SH1 - SH3 Differential Set Point
The SH differential sets how many degrees below the offset
the temperature has to drop before the boiler turns back
on. This parameter can only be changed by the installer by
accessing the
SH1, 2 and 3 Differential Set point parameters
.
The range is 0°F to 60°F. The default is 20°F.
CAUTION
Mixing valves are required for the
protection of any low temperature loops.
NOTICE
Never put the Freeze Protection Pump
on a setting lower than the Freeze
Protection Burner On setting.
NOTICE
Never put the Freeze Protection Pump
on a setting lower than the Freeze
Protection Burner On setting.