22
Test voltage
4 kV AC input against output against power supply
Working voltage
(basic insulation)
600 V AC across all circuits, with overvoltage category II
and pollution degree 2 according to EN 61010-1.
For applications with high working voltages, take measures
to prevent accidental contact and make sure that there is
sufficient distance or insulation between adjacent devices.
Protection against electric
shock
Protective separation according to EN 61140 through
reinforced insulation according to EN 61010-1 for
overvoltage category II and pollution degree 2.
Working voltages: up to 300 V AC/DC across input and
output and across output and power supply.
For applications with high working voltages, take measures
to prevent accidental contact and make sure that there is
sufficient distance or insulation between adjacent devices.
EMC
2)
EN 61326-1 (industry)
Surge withstand
5 kV, 1.2/50 µs, according to IEC 255-4
Ambient temperature
Operation
-10 ... +70 °C
Transport and storage
-40 ... +85 °C
Altitude up to 2000 m
Power supply
22 ... 230 V AC/DC ± 10 % (48 ... 62 Hz), DC < 1.5 W, AC < 4 VA
Design
Modular housing
See dimension drawings for dimensions
Содержание VariTrans P15000H1-KTA
Страница 6: ...6 6 Abmessungen Metallschloss zur Befestigung auf der Hutschiene steckbare Schraubklemmen ...
Страница 12: ...12 ...
Страница 18: ...18 6 Dimensions Metal interlock to attach to mounting rail Pluggable screw terminals All dimensions in mm ...
Страница 24: ...24 ...
Страница 30: ...30 6 Dimensions Verrou métallique pour fixation sur le rail DIN Bornes à vis enfichables ...