P45000
31
6.11 Further Data
EMC
Rail applications
EN 50121-1, EN 50121-3-2, EN 50121-5
Industrial applications
EN 61326-1, EN 61326-3-1
Emitted interference
Class B (up to 110 V DC/to 230 V AC)
Immunity to interference
Industrial applications
Mechanical load
Shock and vibration
According to EN 61373, IEC 61373
Category 1, Class B
tested by independent test laboratory
Fire protection
EN 45545-1, EN 45545-2, EN 45545-5
For exterior applications (combustible mass < 400 g) up to HL3
For interior applications: Mounting in closed and fire-protected control cabinets
Certified by independent test laboratory
Functional safety
Type A device according to EN 61508
Interference immunity requirements for safety-related systems EN 61326-3-1:2017
Reinforced insulation between input and output
Test interval (proof test in-
terval)
20 years
Service life
20 years, L4 according to EN 50155
Signal transmission within
specifications
Single operation
SIL 2 (2 ) (HFT = 0)
Redundant operation
(1oo2 configuration)
SIL 2 (SC 2), SIL 3 (SC 3) (HFT = 1)
Cutoff frequency of the
low-pass filter provided
f
-3dB
≤ 200 Hz
MTBF/MTTF according to EN 61709
Single operation
209 years
Side by side operation
(group of 3 devices)
68 years
Requirements
Stationary operation in well-kept spaces
No ventilation
Continuous operation
45 °C average ambient temperature
Design
Surface mount housing, optionally with mounting on 35-mm DIN rail
Contact protection
Input
Output/power supply
P45***K2*0*
1)
:
IP00
IP20
P45***K2*1*
1)
:
IP54
IP20
Encapsulation
Electronics completely encapsulated by potting with a silicone-free polyurethane cast-
ing resin
Hazardous substances
It contains no hazardous substances according to the REACH Regulation
(EC 1907/2006, 1688/2016).
The restriction of hazardous substances according to the RoHS Directive (2011/65/EU)
is complied with.
1)
The individual product type can be determined from the order description, indicated on the narrow side of the
product (device front), and the product key.