background image

THE-1102 

Installation Guide

cover. Do not use excessive force and deform or 

break the tab. 

2.  Carefully pull the cover from the base.

Handy Box Installation (Recommended)

1.  Mount an HMO-6036 

wall plate to the handy 

box using the two screws 

provided.

2.  Remove the THE-1102’s 

cover from the black base 

(see the Location and 

Cover Removal section).

3.  With the plastic tab button on the bottom, attach 

the base to the backplate using the two screws 

provided.

4.  Connect the wiring (see the Wiring section).
5.  Reinstall the cover.

Hollow Wall Installation

1.  Remove the THE-1102’s cover from the black base 

(see the Location and Cover Removal section).

2.  Using the base as a 

template, drill two holes 

for mounting screws 

(7/64 inches or 3 mm in 

diameter and 1.4 inches, 

1-13/32 inches, or 35.6 mm 

apart) and cut a center 

hole for the terminal block.

3.  With the plastic tab button on the bottom, attach 

the base to the wall using two #6 self-threading 

screws. (Plastic anchors are recommended, and 

the size of the holes will then need adjusting.)

4.  Connect the wiring (see the Wiring section).
5.  Reinstall the cover.

Installation Guide

Humidity Transmitter w/ Temperature Sensor

THE-1102 

 

Mounting

Mounting 

1

Location and Cover Removal  1
Handy Box Installation (Recommended) 

1

Hollow Wall Installation  1

Wiring 

2

More Information  2
Maintenance 

2

Important Notices  2

Location and Cover Removal

Install the THE-1102 on an inside wall where it can 

sense the average room temperature/humidity and 

be away from direct sunlight, heat sources, windows, 

air vents, and air circulation obstructions (curtains, 

furniture, etc.). It can be mounted on a hollow wall 

or (with an HMO-6036) to a 2 x 4 inch handy box.
The cover is held to the black base by three small 

pegs that fit in the holes of the cover. The bottom peg 

is on a tab and snaps into the center bottom hole.
1.  With a small Phillips screwdriver or hex wrench, 

press in and hold the plastic tab button that 

snaps into the center hole on the bottom of the 

2-1/4" (57 mm)

2-7/16"

(62 mm)

5/8"

(16 mm)

Up (Toward Ceiling 

at Installation)

Tab Button

Temperature Output

(10K Thermistor)

Humidity Output

(0 to 5 VDC)

Signal Ground

– Power Ground

(A)

(B)

(C)

(F)

(D)

+ 10 to 15 VDC Power

NOTE:  The Thermistor 

Temperature 

Output 

Terminal “A” 

should be 

at the top of 

the terminal 

strip after 

installation.

Отзывы: