KMC Controls STE-6014 Скачать руководство пользователя страница 6

STE-6014/6017/6018/6019/6020 Room Temperature Sensors 

Installation Guide

Setpoint Variable

  1. In the BACstage software main menu, select 

Objects

 > 

Analog Values

.

  2. Click 

Edit

.

  3. Type in a name in the 

Description

 field and/or 

Label

 field.

  4. Click in the 

Units

 column and select 

°F

 

(Fahrenheit) or 

°C

 (Celsius).

  5. Click 

End Edit

.

  6. Click 

Yes

 for “Send Update Notification Now?”

  7. Click 

OK

.

Override Input (Not Applicable to STE-6014)

  1. In the BACstage software main menu, select 

Objects

 > 

Binary

 Values

.

  2. Click 

Edit

.

  3. Type in a name in the 

Description

 field and/or 

Label

 field.

  4. Click in the 

Units

 column and select 

Off/On

 (or 

No/Yes

Stop/Start

Disabled/Enabled

Inactive/Active

 

according to preference).

  5. Click 

End Edit

.

  6. Click 

Yes

 for “Send Update Notification Now?”

  7. Click 

OK

.

NOTE:  For an additional sample application 

of programming override timers, adapt 

the information in the Application Note 

AN0504F Programming Override Timers 

section of the the Digital Designer’s Guide 

(SP-022).

BAC-A1616BC BACnet Building Controller

Tables and Pull-Up Resistors

Select the 10K ohm pull-up resistor jumper posi

-

tion for the corresponding inputs.

 (See the Installa-

tion section of the BAC-A1616ABC Building Control-

ler Installation and Operation Guide for the correct 

jumper position.)
Because the Building Controller has a 0–12 VDC 

total input range, different tables are required than 

in other (0–5 VDC) KMC controllers. Download the 

CSV table files from www.kmccontrols.com and 

import the needed tables as described in the Tables 

section of the BAC-A1616ABC Building Controller 

Installation and Operation Guide. (You must log-in 

to see the zipped tables in Support > Technical > 

Tables on the web site.)

Thermistor Input

  1. In the desired Analog Input setup screen of the 

web page interface, select KMC Type II Degree 

Fahrenheit or KMC Type II Degree Celsius.

  2.  Select the Lookup Table for the Type II 

Thermistor.

  3. For the Fahrenheit scale, the multiplier is 1.8 and 

the offset is 32. For Celsius, the multiplier is 1 and 

the offset is 0.

  4. Click 

Save

.

Setpoint Input

  1. In the desired Analog Input setup screen of the 

web page interface, select No Device and the 

Lookup Table for the STE-6014 Rotary BBC table.

  2. For the Fahrenheit scale, the multiplier is 1.8 and 

the offset is 32. For Celsius, the multiplier is 1 and 

the offset is 0.

  3. Click 

Save

.

Содержание STE-6014

Страница 1: ...sunlight heat sources windows air vents and air circulation obstructions curtains furniture etc It can be mounted on a hollow wall or with a universal backplate HMO 6036 to a 2 x 4 inch handy box The...

Страница 2: ...White 2 N C Lead 1 Orange White Cables crossed 20 AWG Wiring Connect wires as shown for the relevant model STE 6019 6020 Common Ground Thermistor 10k Ohms A B C Potentiometer Override Button D 10 VDC...

Страница 3: ...ct Device Device Tables KMC10K Type II Table 10 Click Edit 11 Click Defaults values will fill in 12 Click End Edit 13 Click Yes for Send Update Notification Now 14 Click OK Setpoint Input 1 In the BAC...

Страница 4: ...2 68 90 0 32 2 69 90 0 32 2 70 90 0 32 2 71 90 0 32 2 72 90 0 32 2 73 90 0 32 2 74 90 0 32 2 75 90 0 32 2 76 90 0 32 2 77 90 0 32 2 78 90 0 32 2 79 90 0 32 2 80 90 0 32 2 81 90 0 32 2 82 90 0 32 2 83...

Страница 5: ...12 90 0 X113 90 0 X114 90 0 X115 90 0 X116 90 0 X117 90 0 X118 90 0 X119 90 0 X120 90 0 X121 90 0 X122 90 0 X123 90 0 X124 90 0 X125 90 0 X126 90 0 X127 90 0 X128 90 0 NOTE These tables are NOT also f...

Страница 6: ...m pull up resistor jumper posi tion for the corresponding inputs See the Installa tion section of the BAC A1616ABC Building Control ler Installation and Operation Guide for the correct jumper position...

Страница 7: ...00 54 12 2 2 0 32 58 14 4 3 0 77 62 16 7 4 1 14 66 18 9 5 1 47 70 21 1 6 1 74 74 23 3 7 1 97 78 25 6 8 2 16 82 27 8 9 2 31 86 30 0 10 2 42 90 32 2 11 5 00 90 32 2 15 Click OK WinControl Software Ther...

Страница 8: ...Units which opens the Configure Variables screen 5 Select Type Digital 6 Select Off On or No Yes Stop Start Dis Enabled according to preference 7 Click OK 8 Click End Edit 9 Click OK Connections Clamp...

Отзывы: