STE-6014/6017/6018/6019/6020 Room Temperature Sensors
6
Installation Guide
Setpoint Variable
1. In the BACstage software main menu, select
Objects
>
Analog Values
.
2. Click
Edit
.
3. Type in a name in the
Description
field and/or
Label
field.
4. Click in the
Units
column and select
°F
(Fahrenheit) or
°C
(Celsius).
5. Click
End Edit
.
6. Click
Yes
for “Send Update Notification Now?”
7. Click
OK
.
Override Input (Not Applicable to STE-6014)
1. In the BACstage software main menu, select
Objects
>
Binary
Values
.
2. Click
Edit
.
3. Type in a name in the
Description
field and/or
Label
field.
4. Click in the
Units
column and select
Off/On
(or
No/Yes
,
Stop/Start
,
Disabled/Enabled
,
Inactive/Active
according to preference).
5. Click
End Edit
.
6. Click
Yes
for “Send Update Notification Now?”
7. Click
OK
.
NOTE: For an additional sample application
of programming override timers, adapt
the information in the Application Note
AN0504F Programming Override Timers
section of the the Digital Designer’s Guide
(SP-022).
BAC-A1616BC BACnet Building Controller
Tables and Pull-Up Resistors
Select the 10K ohm pull-up resistor jumper posi
-
tion for the corresponding inputs.
(See the Installa-
tion section of the BAC-A1616ABC Building Control-
ler Installation and Operation Guide for the correct
jumper position.)
Because the Building Controller has a 0–12 VDC
total input range, different tables are required than
in other (0–5 VDC) KMC controllers. Download the
CSV table files from www.kmccontrols.com and
import the needed tables as described in the Tables
section of the BAC-A1616ABC Building Controller
Installation and Operation Guide. (You must log-in
to see the zipped tables in Support > Technical >
Tables on the web site.)
Thermistor Input
1. In the desired Analog Input setup screen of the
web page interface, select KMC Type II Degree
Fahrenheit or KMC Type II Degree Celsius.
2. Select the Lookup Table for the Type II
Thermistor.
3. For the Fahrenheit scale, the multiplier is 1.8 and
the offset is 32. For Celsius, the multiplier is 1 and
the offset is 0.
4. Click
Save
.
Setpoint Input
1. In the desired Analog Input setup screen of the
web page interface, select No Device and the
Lookup Table for the STE-6014 Rotary BBC table.
2. For the Fahrenheit scale, the multiplier is 1.8 and
the offset is 32. For Celsius, the multiplier is 1 and
the offset is 0.
3. Click
Save
.