STE-6014/6017/6018/6019/6020 Room Temperature Sensors 

Installation Guide

Controller Configuration

Overview

Ensure that the corresponding 10,000 ohm pull-up 

resistors on the controller are selected (switched 

On).

 Consult the controller’s setup instructions for 

information on switching on the pull-up resistors.

Controller configuration instructions are given for 

both WinControl and BACstage. See the relevant 

software section.

BACstage Software

Thermistor Input

  1. In the BACstage software main menu, select 

Objects

 > 

Inputs

.

  2. Click 

Edit

.

  3. Type in a name in the 

Description

 field (up to 32 

characters) and/or 

Label

 field (up to 16 characters).

NOTE:  No two labels or descriptions in a controller 

can be identical.

  4. Select 

Object Type: Analog

 if it is not the default.

  5. Select 

Device Type: KMC10K Type II

.

  6. Select 

Units: °F

 or 

°C

.

  7. Click 

End Edit

.

  8. Click 

Yes

 for “Send Update Notification Now?”

  9. In the BACstage software main menu, select 

Device

 > 

Device Tables

 > 

KMC10K Type II Table

.

10. Click 

Edit

.

11. Click 

Defaults

 (values will fill in).

12. Click 

End Edit

.

13. Click 

Yes

 for “Send Update Notification Now?”

14. Click 

OK

.

Setpoint Input

  1. In the BACstage software main menu, select 

Objects

 > 

Inputs

.

  2. Click 

Edit

.

  3. Type in a name in the 

Description

 field and/or 

Label

 field.

  4. Select 

Object Type: Analog

 if it is not the default.

  5. Select 

Device

 > 

Device Tables

 > 

Table x (4 or 5)

.

  6. Select 

Units: °F

 or 

°C

.

  7. Click 

End Edit

.

  8. Click 

Yes

 for “Send Update Notification Now?”

  9. In the BACstage software main menu, select 

Device

 > 

Device Tables

 > 

Table x

.

10. Click 

Edit

.

11. Enter the following values in Table x:

NOTE:  In the Adobe Acrobat file of this 

document, you can use the table on pa

ge 

5 to copy and paste the 128 lines int

o the 

appropriate section of the BACstage *.BAC 

panel file (instead of typing in the values 

from the table below).

Index

°F Value °C Value

1

54.0

12.2

2

54.3

12.4

3

54.6

12.6

4

54.9

12.7

5

55.2

12.9

6

55.5

13.1

7

55.8

13.2

8

56.1

13.4

9

56.4

13.6

10

56.7

13.7

11

57.1

13.9

12

57.4

14.1

13

57.7

14.3

14

58.1

14.5

15

58.4

14.7

NOTE:  This table is NOT also for the STE-

6012/6016.

Содержание STE-6014

Страница 1: ...sunlight heat sources windows air vents and air circulation obstructions curtains furniture etc It can be mounted on a hollow wall or with a universal backplate HMO 6036 to a 2 x 4 inch handy box The...

Страница 2: ...White 2 N C Lead 1 Orange White Cables crossed 20 AWG Wiring Connect wires as shown for the relevant model STE 6019 6020 Common Ground Thermistor 10k Ohms A B C Potentiometer Override Button D 10 VDC...

Страница 3: ...ct Device Device Tables KMC10K Type II Table 10 Click Edit 11 Click Defaults values will fill in 12 Click End Edit 13 Click Yes for Send Update Notification Now 14 Click OK Setpoint Input 1 In the BAC...

Страница 4: ...2 68 90 0 32 2 69 90 0 32 2 70 90 0 32 2 71 90 0 32 2 72 90 0 32 2 73 90 0 32 2 74 90 0 32 2 75 90 0 32 2 76 90 0 32 2 77 90 0 32 2 78 90 0 32 2 79 90 0 32 2 80 90 0 32 2 81 90 0 32 2 82 90 0 32 2 83...

Страница 5: ...12 90 0 X113 90 0 X114 90 0 X115 90 0 X116 90 0 X117 90 0 X118 90 0 X119 90 0 X120 90 0 X121 90 0 X122 90 0 X123 90 0 X124 90 0 X125 90 0 X126 90 0 X127 90 0 X128 90 0 NOTE These tables are NOT also f...

Страница 6: ...m pull up resistor jumper posi tion for the corresponding inputs See the Installa tion section of the BAC A1616ABC Building Control ler Installation and Operation Guide for the correct jumper position...

Страница 7: ...00 54 12 2 2 0 32 58 14 4 3 0 77 62 16 7 4 1 14 66 18 9 5 1 47 70 21 1 6 1 74 74 23 3 7 1 97 78 25 6 8 2 16 82 27 8 9 2 31 86 30 0 10 2 42 90 32 2 11 5 00 90 32 2 15 Click OK WinControl Software Ther...

Страница 8: ...Units which opens the Configure Variables screen 5 Select Type Digital 6 Select Off On or No Yes Stop Start Dis Enabled according to preference 7 Click OK 8 Click End Edit 9 Click OK Connections Clamp...

Отзывы: