background image

CTC-4001/4004 

Installation Guide

© 2011 KMC Controls, Inc.   

416-019-01B

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Important Notices

The material in this document is for information pur-

poses only. 

The contents and the product it describes 

are subject to change without notice.

 KMC Controls, 

Inc. makes no representations or warranties with respect 

to this document. In no event shall KMC Controls, Inc. 

be liable for any damages, direct or incidental, arising 

out of or related to the use of this document.

Maintenance

Port C has a non-replaceable built-in filter to prevent 

dirt from hindering the switching action of ports 

A and B. If the filter becomes clogged, replace the 

CTC-4001/4004 thermostat. 
No routine maintenance is required. Care should be 

taken to keep the unit clean from dust during instal-

lation. Each component is designed for dependable, 

long-term reliability, and performance. Careful 

installation will also ensure long-term reliability and 

performance.

 CAUTION

Pneumatic devices must be supplied with 
clean, dry control air. Any other medium (e.g., 
oil or moisture contamination) will cause the 
device to fail.

Adjustments and Calibration

Minor adjustment is required if a different setpoint is 

desired.
1.  Turn the setpoint adjustment clockwise to 

increase (counter-clockwise to decrease). The 

range may be moved up 5° F or down 10° F.

2.  Obtain two thermometers and two containers 

of tempered liquid that match the high and low 

temperatures of the new setpoint span.

3.  Move the CTC-4001/4004 thermostat between 

the containers, allowing sufficient time for the 

element to stabilize. 

4.  With the element in the “low” container, turn the 

setpoint adjustment until port B is closed to port 

C. 

5.  Then move it to the “high” container and verify 

that port A is closed to port C.

6.  Minor adjustment will be required in both 

containers to obtain the desired 5° switching 

band.

NOTE:  The CTC-400x is for low-volume 

applications. Ports A and B are each 

restricted with a 0.015" nozzle. 

NOTE:  If the filtered port C on the CTC-400x is 

used as an “output” (as shown in this 

example), the air to ports A and C must be 

from a filtered source or filtered with an 

external filter (such as an HFO-0006). 

Sample Application

M   B

M

RCC-1012

Reversing Relay

M

CTC-16xx 

Thermostat (DA)

CTC-400x Duct Thermostat 
will pass a DA or RA signal 
to the CSC VAV Volume 
Controller when the 
airstream temperature 
switches between heating 
and cooling

To load or CSC Volume 
Controller thermostat input

CTC-400x mounted in 
the airstream (inlet 
side of the VAV box) 

Отзывы: