background image

BAC-9300 Series Controller Installation Guide 

4 925-019-02G

CONNECT POWER

NOTE: 

Follow all local regulations and wiring 

codes.

1. 

Connect a 24 VAC, Class-2 transformer to the 

black power terminal block

 of the controller.

A.  Connect the neutral side of the transformer 

to the controllers 

common terminal

 

⊥ 

17

.

B.  Connect the AC phase side of the 

transformer to the controllers 

phase 

terminal

 

∼ 

18

.

18

17

NOTE: 

Connect only one controller to each 

transformer with 12—24 AWG copper 

wire.

NOTE: 

Use either shielded connecting cables 

or enclose all cables in conduit to 

maintain RF emissions specifications.

NOTE: 

For more information, see 

Sample 

(BAC-9311) Wiring on page 7

 and the 

YouTube video 

KMC Conquest Wiring: 

BAC-9300 Series Unitary Controllers

.

POWER AND COMMUNICATION STATUS

The 

status LEDs

 indicate power connection and 

network communication. The descriptions below 

describe their activity during 

normal operation

 (at 

least 5 to 20 seconds 

after

 power-up/initialization 

or restart).

NOTE: 

If both the green READY LED and the 

amber COMM LED remain OFF, check 

the power and cable connections to the 

controller.

CONNECT (OPTIONAL) MS/TP NETWORK

1. 

For BAC-93x1/93x1C models (only), connect 

the BACnet network to the 

gray BACnet MS/

TP terminal block

 

15

.

15

NOTE: 

Use 18 gauge AWG shielded twisted 

pair cable with maximum capacitance 

of 51 picofarads per foot (0.3 meters) 

for all network wiring (Belden cable 

#82760 or equivalent).

A.  Connect the 

–A

 terminals in parallel with 

all other 

–A

 terminals on the network.

B.  Connect the 

+B

 terminals in parallel with all 

other 

+B

 terminals on the network.

C.  Connect the 

shields

 of the cable together 

at each device using a wire nut or the 

S

 

terminal in KMC BACnet controllers.

2.  Connect the cable shield to a good earth 

ground at 

one end only

.

NOTE: 

For principles and good practices 

when connecting an MS/TP network, 

see 

Planning BACnet Networks 

(Application Note AN0404A

).

NOTE: 

The EOL switch is shipped from the 

factory in the OFF position.

3.  If the controller is at either end of a BACnet 

MS/TP network (only one wire under the 

terminals), turn the 

EOL

 

switch

 

16

 

to 

ON

.

NOTE: 

For more information, see 

Sample 

(BAC-9311) Wiring on page 7

 and the 

YouTube video 

KMC Conquest Wiring: 

BAC-9300 Series Unitary Controllers

.

16

Содержание BAC-9300 Series

Страница 1: ...formation see the KMC Conquest Controller Application Guide MOUNT CONTROLLER NOTE Mount the controller inside a metal enclosure for RF shielding and physical protection NOTE To mount the controller with screws on a flat surface complete the steps in On a Flat Surface on page 1 Or to mount the controller on a 35 mm DIN rail such as integrated in an HCO 1103 enclosure complete the steps in On a DIN ...

Страница 2: ...relevant installation guide for additional details 7 1 Plug an Ethernet patch cable 7 connected to an STE 9000 Series or STE 6010 6014 6017 sensor into the yellow ROOM SENSOR port 8 of the controller NOTE The Ethernet patch cable should be a maximum of 150 feet 45 meters CAUTION On Conquest E models do NOT plug a cable meant for Ethernet communications into the Room Sensor port The Room Sensor por...

Страница 3: ...nformation NOTE On newer models the Room Sensor port is yellow 8 instead of black to help differentiate it from the black Ethernet ports NOTE For more information see Sample BAC 9311 Wiring on page 7 and the YouTube video KMC Conquest Wiring BAC 9300 Series Unitary Controllers 14 CAUTION Do NOT connect 24 VAC to the analog outputs UO7 UO10 and GNDs NOTE Use 24 VAC only with triac outputs BO1 BO6 w...

Страница 4: ... the amber COMM LED remain OFF check the power and cable connections to the controller CONNECT OPTIONAL MS TP NETWORK 1 For BAC 93x1 93x1C models only connect the BACnet network to the gray BACnet MS TP terminal block 15 15 NOTE Use 18 gauge AWG shielded twisted pair cable with maximum capacitance of 51 picofarads per foot 0 3 meters for all network wiring Belden cable 82760 or equivalent A Connec...

Страница 5: ...etwork 22 21 Amber ETHERNET LED 22 The amber Ethernet LED flashes when the controller is communicating with a 100BaseT Ethernet network The amber Ethernet LED remains OFF when the powered controller is communicating with the network at only 10 Mbps instead of 100 Mbps NOTE If both the green and amber Ethernet LEDs remain OFF check the power and network cable connections MS TP NETWORK ISOLATION BUL...

Страница 6: ...mate K factor from the chart in the Appendix K Factors for VAV section in the KMC Conquest Controller Application Guide For instructions on VAV balancing With an STE 9000 series NetSensor see the VAV Airflow Balancing with an STE 9xx1 section of the KMC Conquest Controller Application Guide With a BAC 5051E Router see its application and installation guide With KMC Connect or TotalControl see the ...

Страница 7: ...E For Ethernet models connect the controller to the network with a standard Ethernet patch cord NOTE Analog inputs accept 1K or 10K sensors 0 12 VDC or 4 20 mA NOTE For more wiring examples see the wiring diagrams that are part of the application library in KMC Connect Converge or TotalControl Early models shown in the drawings had different terminal locations Follow the terminal labels not locati...

Страница 8: ...ff BO5 Binary Heating Valve On Off BO6 Binary Output 6 BO6 Binary Output 6 AO7 and BO4 are controlled simultaneously AO8 and BO5 are controlled simultaneously AO7 and BO4 are controlled simultaneously AO8 and BO5 are controlled simultaneously BAC 9301 HPU BAC 9311 HPU Inputs Inputs AI1 Space Sensor on Room Sensor port AI1 Space Sensor on Room Sensor port AI2 Space Setpoint Offset on port AI2 Space...

Страница 9: ...tage 2 BO3 Cool Stage 2 BO4 Binary Output 4 BO4 Binary Output 4 BO5 Heating Stage 1 BO5 Heating Stage 1 BO6 Heating Stage 2 BO6 Heating Stage 2 BAC 9311 VAV Inputs AI1 Space Sensor on Room Sensor port AI2 Space Setpoint Offset on port AI3 UI3 Discharge Air Temperature AI4 UI4 Analog Input 4 AI5 UI5 Analog Input 5 AI6 UI6 Analog Input 6 AI7 UI7 Analog Input 7 AI8 UI8 Primary Damper Position AI9 Pri...

Страница 10: ...amages direct or incidental arising out of or related to the use of this document The KMC logo is a registered trademark of KMC Controls Inc All rights reserved TEL 574 831 5250 FAX 574 831 5252 EMAIL info kmccontrols com REPLACEMENT PARTS HPO 0055 Replacement Network Bulb Module for Conquest Controllers Pack of 5 HPO 9901 Conquest Hardware Replacement Parts Kit NOTE HPO 9901 includes the followin...

Отзывы: