BAC-19xxxx FlexStat Installation Guide 

6 926-019-02C

(See Illustration 11.) 

For the relay 

circuit, the phase side of the AC 

should be connected to the SC 

terminal.

 FlexStat relays are NO, SPST 

(Form “A”).

NOTE: Unused analog outputs can be 

converted to binary outputs by right-

clicking the output object in KMC 

software and selecting Convert to 

Binary Object.

   CAUTION 

Do not attach a device that draws 

current exceeding the FlexStat’s 

output capacity:

•  Maximum output current for 

individual ANALOG/UNIVERSAL 

outputs is 100 mA (at 0–12 VDC) or 

100 mA total for all analog outputs.

•  Max. output current is 1 A for 

individual RELAYS at 24 VAC/VDC 

or a total of 1.5 A for relays 1–3 or 

4–6.

   CAUTION 

Relays are for Class-2 voltages (24 

VAC) only. Do not connect line voltage 

to the relays!

   CAUTION 

Do not mistakenly connect 24 VAC to 

an analog output ground. This is not 

the same as a relay’s (SC) Switched 

Common. See the backplate’s 

terminal label for the correct terminal.

POWER CONNECTION

   CAUTION 

To avoid damage from ground loops 

and other communication issues in 

networked MS/TP model FlexStats, 

correct phasing on MS/TP network 

and power connections on ALL the 

networked controllers is critically 

important!

NOTE: 

Follow all local regulations and wiring 

codes.

2.  Connect a 24 VAC, Class-2 transformer (or 

24 VDC power supply) to the power terminals 

(see Illustration 12):

A.  Connect the 

neutral

 side of the transform-

er to the common (–/C) terminal 

.

B.  Connect the AC 

phase

 side of the trans-

former to the phase (~/R)terminal 

∼∼

.

T

Phase

Neutral

FlexStat

Phase

Common

Phase

Common

Transformer

24 VAC

T

Ground

DC 

Power 

Supply

24 VDC

Illustration 12—Power Terminals

NOTE: 

Connect only one controller to each 

transformer with 14—22 AWG copper 

wire.

NOTE: 

For information on principles and 

good practices when connecting 

transformers, see 

Tips for Connecting 

24-Volt Power Application Note 

(AN0604D)

.

NOTE: 

To connect 24 V

DC (–15%, +20%) 

instead of VAC power:

•  Connect 24 

VDC

 to the 

∼∼

 (phase/R) 

terminal.

•  Connect 

GND

 to the 

.(common) 

terminal.

NOTE: 

Use either shielded connecting cables 

or enclose all cables in conduit to 

maintain RF emissions specifications.

NOTE: 

If power is applied to the terminals, 

the FlexStat will power up when it 

is reinstalled on the backplate. See 

Mounting on page 2

.

Содержание BAC-19 FlexStat Series

Страница 1: ...g an older FlexStat replace the backplate as well NOTICE OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES KMCConquestTM Automation Hardware QUICK START Complete the following steps to select and install a KMC Conquest BAC 19xxxx FlexStat 1 Select the appropriate model for the intended application and options see the BAC 190000 Series FlexStats Data Sheet at kmccontrols com 2 Mount ...

Страница 2: ...outputs e g 12 conductor is recommended Grounds for all the inputs can be combined on one wire MOUNTING A C B Terminal Blocks on Backplate Optional Ethernet Jack on Back of Cover Cover Locking Screw Embossed UP Indicator DIMENSIONS A 3 874 inches 99 4 mm B 5 124 inches 130 1 mm C 1 301 inches 33 0 mm Illustration 1 Dimensions and Mounting Information NOTE For optimum temperature sensor performance...

Страница 3: ...and Wiring Guide and the BAC 19xxxx FlexStat Application Guide Illustration 5 BAC 19xx63 Terminals and Connections B A IN7 IN6 GND IN5 IN4 IN3 GND IN2 Common C Phase R Analog 9 GND 7 9 Analog 8 Analog 7 Relay 6 SC 4 6 Relay 5 Relay 4 Relay 3 SC 1 3 Relay 2 Relay 1 Outputs Wiring Cutout in Backplate MS TP Network Optional Inputs 24 VAC Wiring is dependent on application Ethernet Network Connector O...

Страница 4: ... TP network see Planning BACnet Networks Application Note AN0404A A Connect the A terminals in parallel with all other A terminals on the network B Connect the B terminals in parallel with all other B terminals on the network C Connect the shields of the cable together at each device using a wire nut or the S terminal in other KMC BACnet controllers CAUTION When reinstalling the cover on the backp...

Страница 5: ...PMENT CONNECTIONS Input Connections 1 Wire any additional sensors to the appropriate input terminals See the BAC 19xxxx FlexStat Sequence of Operation and Wiring Guide These applications are the selectable pack aged programs in the BAC 19xxxx models NOTE Use KMC software to properly configure the devices For passive input devices e g switch contacts and 10K ohm thermistors set the termination to t...

Страница 6: ...other communication issues in networked MS TP model FlexStats correct phasing on MS TP network and power connections on ALL the networked controllers is critically important NOTE Follow all local regulations and wiring codes 2 Connect a 24 VAC Class 2 transformer or 24 VDC power supply to the power terminals see Illustration 12 A Connect the neutral side of the transform er to the common C termina...

Страница 7: ... Cool Auto Off Mode Active Heating Setpoint Units F or C Illustration 13 Screen Menus Access Default NOTE Options in menus are dependent on the FlexStat model and selected application Advanced configuration of a FlexStat can be done through software See the BAC 190000 Series FlexStats Data Sheet for the most relevant KMC Controls tool for additional configuring program ming with Control Basic and ...

Страница 8: ...logo is a registered trademark of KMC Controls Inc All rights reserved TEL 574 831 5250 FAX 574 831 5252 EMAIL info kmccontrols com 2022 KMC Controls Inc Specifications and design subject to change without notice 926 019 01C ADDITIONAL RESOURCES The latest support files are always available on the KMC Controls web site www kmccontrols com To see all available files you will need to log in See the ...

Отзывы: