option X/100mA for indirect measurement with special curerent transformers (nominal secondary
current up to 100 mA)
–
optional X/333mV current inputs for split core CTs or flex-probes (RCTs) with nominal output
0.333 V. Aux. supply 5 V for RCT also available.
–
option NOCT measures only voltages, does not have any current inputs. It is possible to use it as a
smart transducer and relay, with memory, to analyse frequency, voltage, harmonics, unbalance and
voltage quality (with PQ module).
one digital input 24V
2x relay or impulse output (option RR, RI or II)
features can be upgraded via external I/O modules (with ModBus Master module)
power supply:
–
option U: 75
÷
275
V
AC
or 85
÷
350
V
DC
–
option L: 24
÷
48
V
AC
or 20
÷
75
V
DC
–
option S: 12
÷
24
V
AC
or 9
÷
36
V
DC
128 samples per period, voltage and current inputs are read continuously without any gaps
50 voltage and current harmonics
evaluation of all usual three-phase and single-phase quantities such as powers (active, reactive, apparent,
distortion, fundamental), power factors, harmonics and THD of voltages and currents etc.
Registration of Measured Data
built-in real-time clock with battery backup
flash memory to record the measured data with a capacity of 512 MB
aggregation interval from 200 milliseconds to 24 hours
records voltage outages
Transfer and Evaluation of Recorded Data
ENVIS software suite available free of charge for configuration and data analysis
system service ENVIS.Online for live data recording.
USB interface for data transmission, device configuration and firmware upgrade
can be equipped with Ethernet (option E), RS-485 serial line (option 4), USB.
2