Klinkmann Unitronics IO-DI8-RO4 Скачать руководство пользователя страница 7

7/03 

IO-DI8-RO4, IO-DI8-RO4-L   

  I / O   E x p a n s i o n   M o d u l e s

 

Unitronics Industrial Automation 

Outputs 

Number of outputs 

4 relay 

Output type 

SPST-NO relay; 230VAC / 24VDC 

Type of relay 

IO-DI8-RO4 

Takamisawa JY-24H-K or NAIS (Matsushita) JQ1AP-24V  
or OMRON G6B-1114P-24VDC 

IO-DI8-RO4-L 

Takamisawa JY-12H-K or NAIS (Matsushita) JQ1AP-12V  
or OMRON G6B-1114P-12VDC 

Isolation

By relay

Status Indicators  

(OUT) 

Red LEDs—Lit when the corresponding output is active. 

Output current 

5A maximum (resistive load) 
1A maximum (inductive load)  

Maximum frequency 

10Hz  

Contact protection 

External precautions required (see above: Increasing Contact Life Span) 

Outputs’ power supply  

IO-DI8-RO4 

IO-DI8-RO4-L 

Nominal operating voltage 

24VDC 

12VDC 

Operating voltage 

20.4 to 28.8VDC 

10.2 to 15.6VDC 

Maximum current consumption 

40mA@24VDC 

75mA@12VDC 

Environmental 

IP20 / NEMA1 

Operating temperature 

0

°

 to 50

°

C (32

°

 to 122

°

F) 

Storage temperature 

-20

°

 to 60

°

 C (-4

°

 to 140

°

F) 

Relative Humidity (RH) 

5% to 95% (non-condensing) 

Dimensions (WxHxD) 

80mm x 93mm x 60mm (3.15” x 3.66” x 2.362”) 

Weight  

164g (5.8oz.) 

Mounting 

Either onto a 35mm DIN-rail or screw- mounted. 

Notes: 

1.

The inputs' LEDs light up only when communication link is established between module and OPLC.

2.

Input #7 can function either as a high-speed counter, a frequency measurer, or as a normal digital input.
When Input #7 is used as a normal digital input, normal input specifications apply.

3.

 

Input #6 can function either as the counter’s reset, or as a normal digital input; in either case, its
specifications are those of a normal digital input.

Содержание Unitronics IO-DI8-RO4

Страница 1: ...ing and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and compete...

Страница 2: ...corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Mounting the Module DIN rail mounting Snap the device onto th...

Страница 3: ...7 03 IO DI8 RO4 IO DI8 RO4 L I O Expansion Modules Unitronics Industrial Automation 3 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Страница 4: ...k all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten enough ...

Страница 5: ...h speed Counter Reset High speed Counter Wiring the Output s Power Supply Outputs Wiring DC supply 1 Connect the positive cable to the V0 terminal and the negative to the 0V terminal A non isolated power supply can be used provided that a 0V signal is connected to the chassis Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin In the event of voltage fluctuations or ...

Страница 6: ...between module and OPLC Blinks when the communication link fails Inputs Number of inputs 8 in one group Input type pnp source or npn sink Galvanic isolation None Status indicators IN Green LEDs Lit when the corresponding input is active See Note 1 Nominal input voltage 24VDC for IO DI8 RO4 12VDC for IO DI8 RO4 L Input voltage IO DI8 RO4 IO DI8 RO4 L pnp source 0 5VDC for Logic 0 17 28 8VDC for Log...

Страница 7: ... L Nominal operating voltage 24VDC 12VDC Operating voltage 20 4 to 28 8VDC 10 2 to 15 6VDC Maximum current consumption 40mA 24VDC 75mA 12VDC Environmental IP20 NEMA1 Operating temperature 0 to 50 C 32 to 122 F Storage temperature 20 to 60 C 4 to 140 F Relative Humidity RH 5 to 95 non condensing Dimensions WxHxD 80mm x 93mm x 60mm 3 15 x 3 66 x 2 362 Weight 164g 5 8oz Mounting Either onto a 35mm DI...

Страница 8: ...nt nor for any use of the Unitronics products referred to herein in any manner deviating from the recommendations made in this document Unitronics assumes no responsibility for the use of any parts components or other ancillary appliances including circuitry other than as recommended hereunder or other than that embodied in the Unitronics product Unitronics retains all rights to its proprietary as...

Отзывы: