Klinkmann Unitronics IO-DI8-RO4 Скачать руководство пользователя страница 5

7/03 

IO-DI8-RO4, IO-DI8-RO4-L   

  I / O   E x p a n s i o n   M o d u l e s

 

Unitronics Industrial Automation 

Digital I/Os 

„

Inputs may be wired as either pnp (source) or npn (sink) inputs.

npn (sink) inputs 

pnp (source) inputs 

0V

+V

Circuit Protection Device

0V

+V

npn (sink)  

high-speed counter/frequency measurer 

pnp (source )  

high-speed counter/frequency measurer 

0V

+V

Circuit Protection Device

High-speed

Counter

Reset

High-speed

Counter

0V

+V

High-speed

Counter

Reset

High-speed

Counter

Wiring the Output’s Power Supply

 

Outputs

 

Wiring DC supply

 

1.

Connect the "positive" cable to the "+V0"
terminal, and the “negative” to the "0V" 
terminal.   

„

A non-isolated power supply can be used
provided that a 0V signal is connected to 
the chassis.  

„

Do not connect the ‘Neutral or ‘Line’
signal of the 110/220VAC to the device’s 
0V pin. 

„

In the event of voltage fluctuations or
non-conformity to voltage power supply 
specifications, connect the device to a 
regulated power supply. 

Circuit Protection

Device

Load

L1, L2, L3 (115/230VAC)

 +V (12/24VDC)

0V

N

0V

N

N

0V

N

0V

Output's

power supply

0V

+V0

Содержание Unitronics IO-DI8-RO4

Страница 1: ...ing and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product in accordance with local and national standards and regulations Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and compete...

Страница 2: ...corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation Mounting the Module DIN rail mounting Snap the device onto th...

Страница 3: ...7 03 IO DI8 RO4 IO DI8 RO4 L I O Expansion Modules Unitronics Industrial Automation 3 4mm 5 8mm 0 228 85mm 3 346 80mm 3 15 68 4mm 2 693 93mm 3 66 4mm x2 0 16 0 16 ...

Страница 4: ...k all wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm 2 for all wiring purposes 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure that a proper connection can be made 4 Tighten enough ...

Страница 5: ...h speed Counter Reset High speed Counter Wiring the Output s Power Supply Outputs Wiring DC supply 1 Connect the positive cable to the V0 terminal and the negative to the 0V terminal A non isolated power supply can be used provided that a 0V signal is connected to the chassis Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin In the event of voltage fluctuations or ...

Страница 6: ...between module and OPLC Blinks when the communication link fails Inputs Number of inputs 8 in one group Input type pnp source or npn sink Galvanic isolation None Status indicators IN Green LEDs Lit when the corresponding input is active See Note 1 Nominal input voltage 24VDC for IO DI8 RO4 12VDC for IO DI8 RO4 L Input voltage IO DI8 RO4 IO DI8 RO4 L pnp source 0 5VDC for Logic 0 17 28 8VDC for Log...

Страница 7: ... L Nominal operating voltage 24VDC 12VDC Operating voltage 20 4 to 28 8VDC 10 2 to 15 6VDC Maximum current consumption 40mA 24VDC 75mA 12VDC Environmental IP20 NEMA1 Operating temperature 0 to 50 C 32 to 122 F Storage temperature 20 to 60 C 4 to 140 F Relative Humidity RH 5 to 95 non condensing Dimensions WxHxD 80mm x 93mm x 60mm 3 15 x 3 66 x 2 362 Weight 164g 5 8oz Mounting Either onto a 35mm DI...

Страница 8: ...nt nor for any use of the Unitronics products referred to herein in any manner deviating from the recommendations made in this document Unitronics assumes no responsibility for the use of any parts components or other ancillary appliances including circuitry other than as recommended hereunder or other than that embodied in the Unitronics product Unitronics retains all rights to its proprietary as...

Отзывы: