explosion-proof duct fan

  WP-11/Ex  

 

 

 

CAUTIONS

1

.

  

supply voltage 3x400V; 50Hz 

2

.  continuous work 

S1

 

3

.  ingress protection  

IP44 

4

.  ambient temperature:  

-20

 up to  

+40

ºC

 

5

.  systems and appliances used in areas of explosion 

     hazard should be manufactured in conformity with: 

     

  2014/34/EC ATEX  Directive  

     

  valid standards and regulations 

 
In case of WP-11/Ex fans, the motor housing ought to 
be connected with the fan housing by means of the  

G-Y: Kol 6/6 + H05V-K + Kol 6/6

  according to the me- 

chanical documentation 
 
 
A1 

– terminal box in Ex execution 

        TB-P2/P0048 QUINTEX 
 
 
Cables 

W1

 and 

W2

 ought to be selected by the investor. 

The way of connection and the target connection 
of the motor windings should be performed by investor 
too. 
 
 

*

 

S1

 

– isolating switch in Ex execution 

It is suggested to install the isolating switch in a place 
near the fan. Its purchase and installing have to be  
carried out by the investor. 
 
 

CAUTION

The windings of the motor should be connected in accor- 
dance with the data on the nominal plate of the motor and 
with the Connection Diagram that is placed on the fan. 

Fig. No.4  

–  WP-11/Ex  –  Connection Diagram  

 
Prior the fan start-up check subsequent aspects

a/ 

if all mechanical connections are performed correctly 

b/ 

correctness of electrical connection, sequence of phases 

c/ 

correctness of the connections of the motor and the housing to the PE protective cable 

 
After the fan is started, check the impeller rotation sense with reference to the arrow. 

 

 

Содержание WP-11/Ex

Страница 1: ...2 Application 3 3 Reservations of Producer 3 4 Technical Data 4 5 Structure and Function 5 6 Assembly and Start up 5 7 Operational Use 8 8 Troubleshooting Guide 9 9 Maintenance 9 10 Occupational Healt...

Страница 2: ...of February 26th 2014 on the harmonisation of the laws of Member States relating to equipment and protective systems intended for use in potentially explosive atmospheres Journal of Laws EC L96 of 29...

Страница 3: ...factories in areas of explosion hazard but this cannot be methane firedamp hazard neither carbon dust occurrence category 2 the device is designed for application in areas where explosive atmosphe re...

Страница 4: ...eed the nominal rotations I Manufacturer is not responsible for wounds injuries body laceration experienced by User or personnel during the improper operational use 4 Technical Data Table No 1 Type Ro...

Страница 5: ...ckage check the state of the fan if there are no damages that occurred during the transport WP 11 Ex duct fans are installed inside the rooms indoor application in vertical and horizontal round rigid...

Страница 6: ...lations of Occupational and Health Safety and with the instructions given in Fig No4 CAUTION The fan is equipped with protective cables that should be connected to the ventila tion ducts Additionally...

Страница 7: ...nnection and the target connection of the motor windings should be performed by investor too S1 isolating switch in Ex execution It is suggested to install the isolating switch in a place near the fan...

Страница 8: ...tor Following use of the fan is treated as incorrect a conveying the aggressive media b forwarding the media of high dustiness or contaminant particles content c use of the fan in area where the ambie...

Страница 9: ...it the fan to technical revision in regular periods of time Technical revisions on the fan must be executed by a qualified person with adequate authorization Additionally the fan necessarily should by...

Страница 10: ...se garment clothing or putting the hand towards the open inlet of the running fan can cause hazard of accident and severe disabi lity 11 Transport and Storage WP 11 Ex ought to be wrapped in foil and...

Страница 11: ...Electrical equipment of machines Part 1 Gene ral requirements EN ISO 13857 2010 Safety of machinery Safe distances to prevent hazard zones from be ing reached by upper and lower limbs EN 80079 0 2013...

Страница 12: ...12 explosion proof duct fan WP 11 Ex 04 06 2019 NOTES...

Отзывы: