Klimawent WP-10-D/Ex Скачать руководство пользователя страница 9

 

 

 

 

 

 

18.10.2016 

    

Ex-proof roof fans

  WP-

-D/Ex 

 

 

7.

 

Operational Use 

 

Construction of the device assures a reliable function without continuous technical supervi- 
sion.  It is important to check systematically the mechanical and electrical connections, the  
state of grounding  and also to ensure an efficient cooling for the motor. 

 
Incorrect use of the device

:

 

a

/

 

forwarding the media of temperature exceeding the admissible temperature (+60

C), 

b

/

 

conveying the aggressive media, 

c

/

 

forwarding the media of high dustiness or with high fraction of pollution particles, 

d

/

 

use of the fan in a place where the ambient temperature is higher then +40

C. 

 

Consequences of the incorrect use

:

 

– 

damage of the bearings, 

– 

damages caused by corrosion, 

– 

loss in balance of the rotating elements, 

– 

vibrations, 

– 

deformations, 

– 

damages caused by friction. 

 

Risks which can occur due to improper use

:

 

– 

damages and other defects caused by 

 

 

burst of the impeller, 

 

 

break of the shaft, 

 

 

fatigue crack of the material, 

 

 

ignition and explosion caused by sparks. 

  
 

 

8.

 

Troubleshooting Guide 

 

 

Problem 

 

Possible reason 

 

Corrective action  

1. 

Sudden drop of the 

a. 

Obstacle objects, pollutants 

a. 

Clean the ventilation conduit. 

 

intake flow efficiency. 

 

reducing the air flow 

 

 

 

 

 

got stuck at the inlet fitting piece. 

 

 

2. 

Sudden vibrations 

a. 

Obstacle objects reducing  

a. 

Disconnect the fan from  

 

of the fan occur. 

 

the air flow got stuck  

 

the power system, 

 

 

 

in the impeller. 

 

and remove the obstacle. 

 

 

 

 

 

 

 

 

b. 

Impeller is defective. 

b. 

Replace the impeller 

 

 

 

 

 

with motor for a new. 

 
 

 

 

 

Содержание WP-10-D/Ex

Страница 1: ...1 18 10 2016 Ex proof roof fans WP D Ex Use and Maintenance Manual Explosion proof roof fans WP D Ex ATEX mark II 2 G c Ex e ll T3...

Страница 2: ...servations of Producer 5 4 Technical Data 5 5 Structure and Function 7 6 Assembly and Start up 7 7 Operational Use 9 8 Troubleshooting Guide 9 9 Maintenance 10 10 Occupational Health and Safety 10 11...

Страница 3: ...vailable on the market of electrical equipment designed within certain voltage limits Journal of Laws EC L96 of 29 03 2014 2014 34 EC ATEX Directive of the European Parliament and of the Council of Fe...

Страница 4: ...pheres are possible to occur It can be applied in zones 1 2 G the appliance is marked on the Ex classification board II 2 G c Ex e II T3 Marking of the operational conditions of the device group categ...

Страница 5: ...er rotations should not exceed the nominal rotations I Producer is not responsible for wounds injuries body laceration experienced by User or personnel during the improper operational use 4 Technical...

Страница 6: ...6 5 480 130 500 WP 5 D Ex 915 525 60 160 160 194 6 6 5 480 140 WP 7 D Ex 965 570 60 200 160 194 6 6 5 510 155 WP 8 D Ex 990 600 60 200 200 224 8 8 5 535 155 WP 9 D Ex 1030 665 60 200 200 224 8 8 5 580...

Страница 7: ...to lead the electrostatic charges away On the motor housing is located a clamp to fasten the protective cable Additionally on the motor housing is a connection box of the power supply The hemi spheri...

Страница 8: ...l connections are performed correctly b Examine the connection correctness of the electrical connections phases sequence c Check the correctness of the connection between the motor and the PE protecti...

Страница 9: ...nces of the incorrect use damage of the bearings damages caused by corrosion loss in balance of the rotating elements vibrations deformations damages caused by friction Risks which can occur due to im...

Страница 10: ...r supply system Examption from this is a test to carried out on the running fan for example vibration measuring In this case especially follow the rules of Occupational Health and Safety wait until th...

Страница 11: ...ld have destructive effect on the insulation elements constructional elements of the motor and the fan maximum relative humidity should not exceed 80 at the temperature 20 C the ambient temperature sh...

Страница 12: ...12 Ex proof roof fans WP D Ex 18 10 2016...

Страница 13: ...WP 3 D Ex II 2G EExe II T3 3000 0 37 1 0 18 2 BESEL WP 5 D Ex II 2G EExe II T3 3000 0 55 1 4 12 0 BESEL WP 7 D Ex II 2G EExe II T3 3000 1 1 2 4 7 2 BESEL WP 8 D Ex II 2G EExe II T3 3000 1 5 3 5 10 0 I...

Страница 14: ...9 03 2014 The device has been constructed and produced on the basis of subsequent standards PN EN ISO 12100 2012 Safety of machinery Basic concepts general principles for design Risk assessment and ri...

Страница 15: ...15 18 10 2016 Ex proof roof fans WP D Ex NOTES...

Страница 16: ...58 629 64 80 fax 058 629 64 19 e mail klimawent klimawent com pl www klimawent com pl 808W49 WP 3 D Ex 18 10 2016 EN 808W50 WP 5 D Ex 18 10 2016 EN 808W51 WP 7 D Ex 18 10 2016 EN 808W52 WP 8 D Ex 18 1...

Отзывы: