background image

FIRE DAMPERS

362

363

Design changes reserved

80

Installation material: Fire damper FDC25, Mineral wool >140kg/m

3

, Fire protection coating, (HILTI weichschott system) 

Installation steps:

• 

Recommended wall opening for fire damper installation 

is 

Ø

 + 400mm, but openings from 

Ø

 +80…600 mm 

can also be used 

• 

Insert fire damper into wall

• 

Damper blade must be closed during installation!!!

• 

Space between casing and wall close with three layers 

of  mineral wool (density 140 kg/m

3

 or more, coated 

on one side)

• 

Cut additional 50 mm thick rings to cover fire damper 

perimeter from both sides

• 

Connections of mineral wool seal with intumescent fire 

resistant sealant 

• 

Mineral wool and damper casing must be coated with 2 

mm thick fire protection coating  

• 

Actuator and release unit must not be coated!!!

• 

Test the fire damper after the installation

Fire protection coating

Mineral wool insulation

1
2

After installation check for damper
blade mobility, preform an opening and
closing test.

3
4

Fire damper FDC25

Wall, according to table 1

Installation in a rigid wall (mortarless)

1

2

3

4

Installation steps:

• 

Recommended ceiling opening for fire damper 

installation is Øn+ 160mm, but openings from Øn 

+80*…200 mm can also be used 

(*decrease under 

specified value in opening size is allowed if there is 

sufficient room for seal installation)

• 

Insert fire damper into ceiling and secure on ceiling face 

with two hinges that are placed on the top of fire damper 

casing. Hinges are used to hold only damper during 

installation! (for max. distance from wall 80 mm) 

• 

Damper blade must be closed during installation 

• 

Space between casing and ceiling must be filled with 

mortar, gypsum or concrete

• 

Test the fire damper after the installation 

• 

During installation, manual or motorized mechanism 

must be protected from mortar, gypsum or concrete. 

After installation check for damper
blade mobility, preform an opening and
closing test.

Standard mortar or gypsum

1
2
3

Fire damper FDC25

Ceiling, according to table 1

Installation in ceiling (mortar based)

1

3

2

Содержание FD25-E

Страница 1: ...355 www klimaoprema hr FDC25 FIRE DAMPER 7 S4 v 2 9 en...

Страница 2: ...ased 361 Installation in a flexible wall mortar based 361 Installation in ceiling mortar based 362 Installation in a rigid wall mortarless 362 Installation in a flexible wall mortarless 363 Installati...

Страница 3: ...with greater fire resistance can also be used Fire damper should be installed according instal lation manual which can be found within this document Table 1 Dimensions FIRE DAMPER FDC25 Standard diam...

Страница 4: ...sm type R manual mechanism E230 solenoid actuator AC230V E24 solenoid actuator AC 24V M230 electric actuator AC230V M24 electric actuator AC DC 24V Options s electric limit switches indicating damper...

Страница 5: ...er blade 2 electric actuator Belimo BLF 3 thermo electric tripping device 72 C 4 intumescent strip 5 Options M230 electric actuator AC 230V M24 electric actuator AC DC 24V FDC25 R cylindrical fire dam...

Страница 6: ...zed steel but on demand can be made from Galvanized steel and powder coated Stainless steel Stainless steel and powder coated Fire damper for areas with potentially explosive atmospheres are also avai...

Страница 7: ...FDC25 Wall according to table 1 Installation steps Recommended wall opening for fire damper installation is 160mm but openings from 80 200 mm can also be used Insert fire damper into wall and secure o...

Страница 8: ...mper blade mobility preform an opening and closing test 3 4 Fire damper FDC25 Wall according to table 1 Installation in a rigid wall mortarless 1 2 3 4 Installation steps Recommended ceiling opening f...

Страница 9: ...ing test 3 4 Fire damper FDC25 Wall according to table 1 Installation material Fire damper FDC25 Mineral wool 140kg m3 Fire protection coating HILTI weichschott system Installation steps Recommended c...

Страница 10: ...ble connectors are being installed very important is to install extension peace if necessary see table 2 ACCESSORIES Suspension for mortarless installation Suspension systems are required for the dry...

Страница 11: ...e supplied with one or two limit switches switches can also be fitted later DAMPER OPEN DAMPER CLOSED Fire damper is shipped with closed damper blade Fire damper with manual actuating mechanism is ope...

Страница 12: ...not move the damper into closed position after power failure ther moelectric fuse switch for checking for proper functioning handle for manual opening Belimo BLF24 T i BF24 T supply via safety isolati...

Страница 13: ...per Level Digital field controller K FC24 Digital field controller to control and monitor up to 4 motorized fire dampers and 4 smoke detectors Communication Modbus RTU RS 485 The safety function of th...

Отзывы:

Похожие инструкции для FD25-E