background image

FIRE DAMPERS

356

357

Design changes reserved

• 

Used for the isolation of duct penetrations between fire compart-

ments. 

• 

Fire dampers consist of housing, fire-resistant damper blade and 

release mechanism. 

• 

Casing made of galvanised sheet steel, damper blade made of 

special insulating material, damper blade shaft and push rod 

made of stainless steel, bearings made of brass, seals made of 

polyurethane and elastomer.

FIRE CLASSIFICATION (according to EN 13501-3)

Fire resistance of fire damper depends on classification of walls or ceilings. It is allowed to install product to walls or ceilings as 

specified in table 1. Walls or ceilings with greater fire resistance can also be used. Fire damper should be installed according instal-

lation manual which can be found within this document.

Table 1

Dimensions

FIRE DAMPER FDC25

Standard diameters

Ø

n

[mm]

100

125

160

200

250

300

315

Wall details 

Sealing

Thickness 

[mm]

Density 

[kg/m

3

]

Dimensions 

BxH [mm]

Classification

Rigid wall

Mortar or gypsum

≥100

650

Ø

100 up to 

Ø315

 

EI 90 S

Rigid wall

(Weichschott) mineral wool >140 kg/m3 
+coating

≥100

650

EI 90 S

Standard plasterboard wall 
(GKB, GKF) 

Mortar or cover boards (Mas-
terboard)

≥100

EI 60 S

Standard plasterboard wall 
(GKF)       

Mortar or cover boards (Mas-
terboard)

≥125

EI 90 S

Standard plasterboard wall 
(GKF)       

(Weichschott) mineral wool >140 kg/m3 
+coating

≥100

EI 90 S

Ceiling

Mortar or gypsum

≥125

650

EI 120 S

Ceiling

(Weichschott) mineral wool >140 kg/m3 
+coating

≥125

650

EI 90 S

Содержание FD25-E

Страница 1: ...355 www klimaoprema hr FDC25 FIRE DAMPER 7 S4 v 2 9 en...

Страница 2: ...ased 361 Installation in a flexible wall mortar based 361 Installation in ceiling mortar based 362 Installation in a rigid wall mortarless 362 Installation in a flexible wall mortarless 363 Installati...

Страница 3: ...with greater fire resistance can also be used Fire damper should be installed according instal lation manual which can be found within this document Table 1 Dimensions FIRE DAMPER FDC25 Standard diam...

Страница 4: ...sm type R manual mechanism E230 solenoid actuator AC230V E24 solenoid actuator AC 24V M230 electric actuator AC230V M24 electric actuator AC DC 24V Options s electric limit switches indicating damper...

Страница 5: ...er blade 2 electric actuator Belimo BLF 3 thermo electric tripping device 72 C 4 intumescent strip 5 Options M230 electric actuator AC 230V M24 electric actuator AC DC 24V FDC25 R cylindrical fire dam...

Страница 6: ...zed steel but on demand can be made from Galvanized steel and powder coated Stainless steel Stainless steel and powder coated Fire damper for areas with potentially explosive atmospheres are also avai...

Страница 7: ...FDC25 Wall according to table 1 Installation steps Recommended wall opening for fire damper installation is 160mm but openings from 80 200 mm can also be used Insert fire damper into wall and secure o...

Страница 8: ...mper blade mobility preform an opening and closing test 3 4 Fire damper FDC25 Wall according to table 1 Installation in a rigid wall mortarless 1 2 3 4 Installation steps Recommended ceiling opening f...

Страница 9: ...ing test 3 4 Fire damper FDC25 Wall according to table 1 Installation material Fire damper FDC25 Mineral wool 140kg m3 Fire protection coating HILTI weichschott system Installation steps Recommended c...

Страница 10: ...ble connectors are being installed very important is to install extension peace if necessary see table 2 ACCESSORIES Suspension for mortarless installation Suspension systems are required for the dry...

Страница 11: ...e supplied with one or two limit switches switches can also be fitted later DAMPER OPEN DAMPER CLOSED Fire damper is shipped with closed damper blade Fire damper with manual actuating mechanism is ope...

Страница 12: ...not move the damper into closed position after power failure ther moelectric fuse switch for checking for proper functioning handle for manual opening Belimo BLF24 T i BF24 T supply via safety isolati...

Страница 13: ...per Level Digital field controller K FC24 Digital field controller to control and monitor up to 4 motorized fire dampers and 4 smoke detectors Communication Modbus RTU RS 485 The safety function of th...

Отзывы: