VII. Initial start
VII. Initial start
VII. Initial start
VII. Initial start----up
up
up
up
1. Turn on main switch 5Q1.
The display needs approx. 15 seconds to activate.
2. The flow meter is bypassed for 15 seconds after the pump starts.
Press reset, if necessary. (Black button on the control cabinet door
(Black button on the control cabinet door
(Black button on the control cabinet door
(Black button on the control cabinet door and
and
and
and ACK
ACK
ACK
ACK
button on the SPS display).
button on the SPS display).
button on the SPS display).
button on the SPS display).
3. The compressor begins running when the water temperature reaches 18.5°C after
30 seconds.
4. When the compressor is running the two condenser vents are released. They are
reactivated once the pressure in the condenser reaches approx. 13 bar. The stop
light on the frequency converter stays lit as long as the vents are off.
5. Vents regulate themselves gradually and independently of the SPS in accordance
with the set condenser pressure.