83003502.Kc ECO_Install_Instruction_V03.odt
Page 36 of 39
10.2
Water pressures
Suction pressure must be between 1.0 bar (14.5 PSI) and 1.5 bar (21.75 PSI).
High pressure on the IFP shall be between 4.0 bar (58 PSI) and 6.0 bar (87 PSI) in Day
Mode.
High pressure on the IFP shall be between 2.0 bar (29 PSI) and 4.0 bar (58 PSI) in Night
Mode.
10.3
Compressor
Check the power consumption.
10.4
Fans
Check the power consumption.
10.5
Refrigerant pressures
The low-pressure side should be between 6.0 bar (87 PSI) and 8.0 bar (116 PSI).
The high-pressure side should be between 18 bar (261 PSI) and 26 bar (377 PSI).
10.6
Temperatures
Outflow water temperatures should be between 19°C (66.2°F) and 22°C (71.6°F).
Inflow water temperatures should be between ~21°C (69.8°F) and ~27.7°C (81.9°F) for
the ECO133L and 21°C (69.8°F) and 25,5°C (77.9°F) for the ECO122L, depending on
the operating state of the MR system.
Be aware that the outlet watertemp. during Nightmode reach 26°C
Содержание ECO 133 L
Страница 8: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 8 of 39 ...
Страница 9: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 9 of 39 ...
Страница 11: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 11 of 39 ...
Страница 12: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 12 of 39 4 5 Dimensions in mm inch ...
Страница 14: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 14 of 39 Do not drill any hole into the unit ...
Страница 21: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 21 of 39 ...
Страница 26: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 26 of 39 Disassembly of the flow limiter ...
Страница 30: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 30 of 39 On the IFP use also the attached brass fittings ...
Страница 37: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 37 of 39 11 Overview water chiller and IFP ...