83003502.Kc ECO_Install_Instruction_V03.odt
Page 28 of 39
Chiller is installed above the IFP panel!
This drawing is only a sketch and is not a exact model down to the last detail!
Before filling the system:
–
Whole system is installed with all options
–
All valves are in open position
–
System is OFF
Read the static pressure of your system
at the pressure gauge on the IFP panel.
Chiller higher than the IFP panel → 1.7–1.8bar
Limitation: 8m above IFP
Chiller on the same level panel → 1.7–1.8bar
The maximum permitted length of the
piping between ECO Chiller and IFP
is 45m one way.
A installed and working automatic Airvent in supply&return piping with a correct static pressure
will determin most of the failures and is recommended for this system.
The heights refer to the base plate of the chiller and the upper edge of the IFP !
Содержание ECO 133 L
Страница 8: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 8 of 39 ...
Страница 9: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 9 of 39 ...
Страница 11: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 11 of 39 ...
Страница 12: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 12 of 39 4 5 Dimensions in mm inch ...
Страница 14: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 14 of 39 Do not drill any hole into the unit ...
Страница 21: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 21 of 39 ...
Страница 26: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 26 of 39 Disassembly of the flow limiter ...
Страница 30: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 30 of 39 On the IFP use also the attached brass fittings ...
Страница 37: ...83003502 Kc ECO_Install_Instruction_V03 odt Page 37 of 39 11 Overview water chiller and IFP ...