30
MIDEX
Kirchgaesser Industrieelektronik GmbH
Controls
4.6.4 Function 4-4: Check the switch outputs
diagnosis
4-4
check switch-out
Function test of all switch outputs by switching active
resp. inactive.
Code number to activate: user
Available values: active / inactive
All switch outputs switch on or off depending on their parameters (active high or active
low).
Example:
switch-out
active
Check the switch outputs in status "active"
4.6.5 Function 4-5: Check the pulse outputs
diagnosis
4-5
check pulse-out
Function test of all pulse outputs.
Code number to activate: user
Available range: 1 .. 60.000 ms
Example:
pulse period
01000 ms
Output pulse period of 1000 ms
4.6.6 Function 4-6: Simulation value of flow rate
diagnosis
4-6
sim. value flow
Simulation value for flow rate.
Code number to activate: user
Example:
sim. value flow
100 m^3/h
Simulation value for flow rate = 100 m³/h
4.6.7 Function 4-7: Simulation flow rate on/off
diagnosis
4-7
simulate flow
Switch the simulation of flow rate on and off.
The medium detection is switched off during the simulation. If MIDEX is fitted out with
a volume counter, please notice the count before simulation and enter this count in
function 3-10 after simulation.
Code number to activate:
user
Example:
simulate flow
active
Simulation flow rate on
Содержание MIDEX-H Series
Страница 42: ...42 MIDEX Kirchgaesser Industrieelektronik GmbH Dimension sheets 6 Dimension sheets ...
Страница 43: ...MIDEX Kirchgaesser Industrieelektronik GmbH 43 Dimension sheets ...
Страница 44: ...44 MIDEX Kirchgaesser Industrieelektronik GmbH Dimension sheets ...
Страница 47: ...MIDEX Kirchgaesser Industrieelektronik GmbH 47 For your notes ...