29
Controls
4.6
Menu 4: Diagnosis
The simulation values of 4.6.6 to 4.6.9 are used as measurands and enter into all cal-
culations. The simulation is only activated after calling the measurand display.
The display shows "Simul." to make clear, that the displayed value is a simulated and
not a measured value.
4.6.1 Function 4-1: Display error memory
diagnosis
4-1
error memory
Display the permanent error memory
Code number to display function:
no
Code number to modify parameters: factory
A deletion of the error memory can be execute in the factory only.
This function is available only for company intern purposes!
4.6.2 Function 4-2: Check frequency outputs
diagnosis
4-2
check freq.-out
Function to test all frequency outputs by entering a test
frequency.
Code number to activate: user
Available range: 4 .. 17 Hz in steps of 1 Hz
Example:
frequency
f = 10 Hz
Test frequency output of 10 Hz
4.6.3 Function 4-3: Check the outputs with limit values
diagnosis
4-3
check limit-out
Function test of all frequency outputs by simulating a
percentage measurand.
Code number to activate: user
Available range: 0 .. 120%
All limit outputs, whose limit values are below the simulated value, switch on or off
depending on their parameters (active high or active low).
Example:
measurand
060%
Check the limit outputs by simulating a measurand of
60%.
Содержание MIDEX-H Series
Страница 42: ...42 MIDEX Kirchgaesser Industrieelektronik GmbH Dimension sheets 6 Dimension sheets ...
Страница 43: ...MIDEX Kirchgaesser Industrieelektronik GmbH 43 Dimension sheets ...
Страница 44: ...44 MIDEX Kirchgaesser Industrieelektronik GmbH Dimension sheets ...
Страница 47: ...MIDEX Kirchgaesser Industrieelektronik GmbH 47 For your notes ...