Vent Termination

NOTE: Clearances are to the edge of terminal plate, add 6-3/4” to
clearances to arrive at center line.
NOTE: Local Codes or Regulations may require different               
clearances.

Termination

It is imperative that the vent termination be located observing the
minimum clearances as shown. There must not be any obstruction such
as bushes, garden sheds, fences, decks or utility buildings within 24”
from the front of the termination plate.
Do not locate termination where excessive snow or ice build-up may
occur. Be sure to check vent termination area after snow falls and clear
to prevent accidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent termination area.

General Venting Information

The gas fireplace is approved to be vented either through the side wall
or vertically through the roof.
This appliance is approved with Kingsman flex vent system and also
approved for use with Simpson Duravent Direct Vent System (model
DV-GS series) and Selkirk Direct Temp.
Kingsman flex vent system can be used with Simpson Duravent Direct
Vent termination’s (model DV-GS series).
When using Simpson Duravent or Selkirk Direct Temp a Kingsman/
Duravent adapter must be used.
ONLY VENTING COMPONENTS SPECIFICALLY APPROVED
AND LABELED FOR THIS FIREPLACE MAY BE USED.

Venting terminal shall not be recessed into a wall or siding.  If finishing
the outside wall with vinyl or wood siding it is recommended that a
Siding Shield be installed, Part Number ZDVSSLR.

1 - In accordance with the current 

CSA B149.1, Natural Gas and Propane Code

.

2 - In accordance with the current 

ANSI Z223.1/NFPA 54, National Fuel Gas Code

.

3 - A vent shall not terminate directly above a sidewalk or paved driveway that is locat-

ed between two single family dwellings and serves both dwellings.

4 - Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of

two sides beneath the floor.

5 - Clearance in accordance with local installation codes and the requirements of the

gas supplier.

Vent Terminal

Air Supply

Area Where Terminal Not Permitted.

A - Clearance above grade, veranda, porch, deck, or balcony 12 inches

(30cm) minimum.

1-2

B - Clearance to window or door that may be opened. 12 inches (30cm) minimum

for appliances 100 000 Btuh (30 kW) and lower, in Canada.  9 inches

2

(23cm) for appliances 50 000 Btuh and lower, in USA.

C - Clearance to permanently closed window minimum 12 inches (30cm)

recommended to prevent condensation on window, in Canada.  9
inches

2

(23cm) for appliances 50 000 Btuh and lower, in USA.

D - Vertical clearance to ventilated soffit located above the termination

within a horizontal distance of 2 feet (60cm) from the center line of the
termination. 18 inches (46cm) minimum.

5

E - Clearance to unventilated soffit 12 inches (30cm) minimum.

F - Clearance under veranda, porch, deck or balcony 12 inches

1

(30cm)

minimum.

4

US

5

G - Clearance from a perpendicular inside wall or outer corner to the

edge of the vent terminal plate is 3” (minimum).

H - Clearance to each side of center line extended above

meter/regulator assembly 3 feet (91cm) within a height 15 feet
(4.5m) above the meter/regulator assembly.

I - Clearance to service regulator vent outlet 3 feet (91cm) minimum.

US

5

J - Clearance to non-mechanical air supply inlet to building or the com-

bustion air inlet to any other appliance: In Canada, 6 inches (15cm)
for appliances ≤10,000 Btuh (3kW), 12 inches

1

(30cm) minimum for

appliances >10,000 Btuh (3kW) and ≤100,000 Btuh (30kW), 36 inch-
es (91cm) for appliances >100,000 Btuh (30kW). In the USA, 6 inch-
es

2

(15cm) for appliances ≤10,000 Btuh (3kW), 9 inches (23cm) for

appliances >10,000 Btuh (3kW) and ≤50,000 Btuh (15kW), 12 inch-
es (30cm) for appliances >50,000 Btuh (15kW).

K - Clearance to a mechanical air supply inlet 6 feet (1.8m) mini-

mum.

1

,in Canada.  In USA, 3 feet (91cm) above if within 10 feet

2

(3m) horizontally.

L - Clearance above paved sidewalk or a paved driveway located on

public property 7 feet (2.1m) minimum.

3

M - Clearance above highest point of exit on roof 18 inches (45cm).

N - Clearance to perpendicular wall 24 inches (60 cm).

(Recommended to prevent re-circulation of exhaust products.  For additional
requirements check local codes.)

V

Содержание MDV30

Страница 1: ...or other flammable vapors and liquids in the vicinity of this or any other appliance What To Do If You Smell Gas Do not try to light any appliance Extinguish any open flame Do not touch any electrical...

Страница 2: ...n between each Be aware during log and firebox paint curing that a white deposit may be developing on the inside of the glass doors It is important to remove this white deposit from the glass doors wi...

Страница 3: ...g Clearances 17 Installation Operation 18 Operation Maintenance 18 Installation Requirements for the Commonwealth of Massachusetts 19 Fan Kit Installation 20 Door and Grill Installation 21 Bay Window...

Страница 4: ...NIT 41 062 PENINSULA UNIT 38 062 TOP VIEW 20 687 TOP VIEW 23 687 50 50 CORNER UNIT R H 38 062 REAR VIEW 16 125 36 125 16 125 21 687 15 50 36 062 29 75 SIDE VIEW END VIEW 32 625 31 875 Unit Dimensions...

Страница 5: ...VERTICAL MAX Horizontal Run With Required Vertical Run LEFT CORNER TOP VIEW LEFT CORNER TOP VIEW MAX 36 0 Horizontal Run With Min Vertical Run RIGHT BURNER SYSTEM LEFT BURNER SYSTEM LEFT BURNER SYSTEM...

Страница 6: ...are equipped with nailing tabs Level Fireplace and nail or screw into place NOTE For Low Profile Enclosure Refer to Page 16 for installation instructions R H FIREPLACE SHOWN FRAMING DETAIL THROUGH Co...

Страница 7: ...k and Glowing Ember installation refer to PAGE 16 FACING MATERIAL INSTALLATION Facing material Example DRYWALL may be installed flush with top of Fireplace Side facing to be installed to standoffs onl...

Страница 8: ...not Load Bearing MIN 36 0 FIGURE 1 FIGURE 2 SEE THROUGH FIREPLACE SHOWN FIREPLACE ASSEMBLY 1 Mount Door Cover Figure 2 First apply a small bead of High Heat Silicone to door seal Mount Door and screw...

Страница 9: ...NG MATERIAL INSTALLATION Facing material Example DRYWALL may be installed Flush with top of Fireplace Side facing to be installed to standoffs only NOTE This UNIT is not Load Bearing Gyprock Gyprock D...

Страница 10: ...8 See Through With CVCK Dimensions Note When CVCK is used a CVCK Kit must be installed on Both sides of the unit See Through With CVCK Enclosures...

Страница 11: ...tom supplies you with two 6 x 8 rectangular holes The use of these holes depends on valve and fireplace location on riser or upper floor Fireplace Assembly 1 Mount Door Cover First apply a bead of Hig...

Страница 12: ...Note When CVCK is used a CVCK Kit must be installed on Both sides of the unit MDV31 with MQ36SWF Surround See Through FRAMING FACING REQUIREMENTS MDV31 with CVCK Clean View Circulating Kit 10...

Страница 13: ...is installed It is recommended that the Leading Edge Screws be installed before the side screws 6 Position the appliance inside the Framing and secure it using the nailing tabs on the CVCK Ensure that...

Страница 14: ...the upper portion of the Surround so that the Surround Ledge is resting on top of the CVCK Deflector Lip 3 Align the Mounting Screw Holes and fasten the Surround in place with the supplied screws 4 At...

Страница 15: ...om fireplace up and to wall sleeve Refer to Page 15 for any additional information FRAMING DETAIL HORIZONTAL RUN WITH MIN VERTICAL RUN MIN 36 0 FIGURE 1 THROUGH COMBUSTIBLE WALL 11 0 11 0 42 0 MIN For...

Страница 16: ...14 FACING MATERIAL INSTALLATION Facing material Example DRYWALL may be installed Flush with top of Fireplace Side facing to be installed to standoffs only DRYWALL...

Страница 17: ...IGHT OF 52 0 MUST BE MAINTAINED FOR PROPER CLEARANCES INSULATION SLEEVE IS NOT REQUIRED THIS WILL LEAVE A 4 0 MINIMUM CLEARANCE TO COMBUSTIBLE TOP It is recommended for Propane Horizontal Installation...

Страница 18: ...P l a t n o z i r o H f o p o T Top Framing from Standoff 0 inches 0mm Louvered Units Only Top of 90 Bend No Sleeve in Enclosure over 52 4 inches 102mm Bottom of Top Enclosure with Insulation Sleeve 4...

Страница 19: ...17...

Страница 20: ...poses and under no circumstances shall they provide a primary heat source Certified for installation in a bedroom or bed sitting room In Canada must be installed with listed milli volt thermostat In U...

Страница 21: ...t terminal must be used and if applicable a Product approved air intake must be used Installation shall be in strict compliance with the manufacturer s instructions A copy of the installation instruct...

Страница 22: ...o bottom pan Refer to diagram for proper location Power cable to be routed through 6 x8 access hole 4 Connect power sensor and variable speed wall switch as shown in wiring diagram SUGGESTED LOCATION...

Страница 23: ...ws in both ends To install slide the head into one of the teardrop slots then slide Grill to opposite side repeat procedure These screws may have to be adjusted for proper alignment and length 3 All G...

Страница 24: ...t on each side as shown in illustration and install Brass Trim CAUTION WARNING WHEN INSTALLING Bay window ASSEMBLY ORIGINAL GLASS WINDOW MUST REMAIN INSTALLED ON FIREPLACE FAILURE TO FOLLOW THESE INST...

Страница 25: ...en exposed to direct flame However care should be taken not to block burner ports Blocked Burner Ports can cause an incorrect flame pattern carbon and delayed ignition If in the event you require addi...

Страница 26: ...Step 2 Take Log 4 and place onto burner using the two log tabs located on burner pan as a guide Step 3 Take Log 1 and place onto burner using the two log tabs located on burner pan as a guide Step 4 P...

Страница 27: ...ilot assembly Step 2 Place flat area of Log 2 up against Tab 2a and rest short branch onto second grate bar Step 3 Locate mounting hole bottom of Log 3 onto Tab 3a and have char area touch Tab 3b TAB...

Страница 28: ...Place V area of Log 5 onto grate bar and rest log onto flat area of Log 2 Step 6 Position Log 6 up against Logs 4 and 5 and place flat area of log on floor of fire box Step 7 Locate notched areas of L...

Страница 29: ...urner as shown Step 1 Place rocks 4 into position as shown Do not place rocks directly over top of the burner tube Step 2 Place rocks 6 into position as shown Step 3 Place rocks 4 into position as sho...

Страница 30: ...e rock 3 that is high lighted over the single porting crossover area as shown Step 7 Place rock 1 into position as shown MQRSP7 Rock Support Platform and MQROCK1 Finished setup and burn If too much fl...

Страница 31: ...of brick on page 16 of Manual OPTIONAL BACK AND SIDE BRICK PANEL INSTALLATIONS 1 Remove side brick clip located on top of firebox 2 Slide side brick panel into firebox through the small side opening a...

Страница 32: ...ove Burner DO NOT force up or sideways as this may damage Venturi FIGURE 2 4 To replace reverse procedure VALVE REMOVAL AND REPLACEMENT 1 To remove Valve first follow Burner instructions 2 Remove GAS...

Страница 33: ...t screw to provide proper sized flame Recommended Maximum Lead Length Double Wire When Using Wall Switch or Thermostat Wire Size Max Length 14 GA 100 FT 16 GA 64 FT 18 GA 40 FT 20 GA 25 FT 22 GA 16 FT...

Страница 34: ...pipe is shown at right 3 When using copper or flex connector use only approved fittings Always pro vide a union so that gas line can be easily disconnected for burner or fan servic ing See gas specif...

Страница 35: ...local installation codes and the requirements of the gas supplier Vent Terminal Air Supply Area Where Terminal Not Permitted A Clearance above grade veranda porch deck or balcony 12 inches 30cm minimu...

Страница 36: ...very 2 feet In off set installation support straps should be used to stabilize pipe Expand 4 and 7 flex pipe to the point that the 7 protrudes approxi mately 2 to 3 inches past outer wall and the 4 fl...

Страница 37: ...llowed 3 Vent table has been established for 90 horizontal vertical runs With use of flex pipe distance not having 90 bends will not fall into vent table standards See Fig B Venting Table From Bottom...

Страница 38: ...ofile enclosure 2 5 rise per ft for horizontal runs with min vertical from Fireplace For installations other than Low Profile Enclosures top of horizontal with no sleeve requires a 2 5 clearance and 4...

Страница 39: ...and nail in place using 1 spiral nails 3 A fire stop must be installed on the bottom side of the joists when passing through a ceiling or floor If an attic insulation shield is to be used a fire stop...

Страница 40: ...306 3800 312 3800 132 3800 134 3800 302 3600 301 5000 P025WS 1000 150GE RED 1000 150MP BLACK 1000 218 Z1MT 3800 128 EMBER I EMBER R ZIRC 3800 173 3800 171 3800 172 3800 138 3800 127 3800 170 3600 115...

Страница 41: ...39 For Models MDV31 39 Replacement Parts continued...

Страница 42: ...40 ZDV48GP ZDV7SC ZDV4SS ZDVRS ZDV7FCL ZDVWT ZDVSS ZDVST ZDV7FC ZDV4FC ZDVAIS ZDVFS ZDVAAF ZDVAF2 ZDVAF3 ZDVFK5 ZDVFK8 ZDVFK20 FDVHT FDVVT40 Replacement Parts continued...

Страница 43: ...ane PART NO DESCRIPTION Log Sets Required for each unit LOGF38 Log Set Five Piece Fibre Split Oak MDV38 Choose Your View Required for each unit M30PK PENINSULA KIT THREE SIDED VIEWING One Large Panel...

Страница 44: ...Two Sets MGSKBA Grill Kit See Through Classic Antique Brass Two Sets MGSKBC Grill Kit See Through Classic Chrome Two Sets MGSKBL Grill Kit See Through Black Two Sets MGSKPB Grill Kit See Through Poli...

Страница 45: ...couple 290 129 SIT unified 1001 P157SI Orifice Pilot LP 977 157 SIT 1001 P159SI Orifice Pilot NG 977 159 SIT 1001 P508SI HT Cable 16 1001 P633SI Valve Nova LP Hi Lo 0820633 651 1001 P634SI Valve Nova...

Страница 46: ...minals at wall switch If burner comes on replace defective Switch ON wall switch If okay jumper wires across wall switch wires at valve If burner comes on wires are faulty or connections are bad Gener...

Страница 47: ...service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoeve...

Отзывы: