background image

 

General information and Guidelines: 

This heater must be properly placed before it is used. 

DO NOT tamper with or change the operating of this 

heater. All service should be preformed by a authorized 

service representative. Only replace components with 

King approved replacement parts.  

Operation: 

1. After the electric heater has been 

safely located

,

thermostat should be turned to LOW or

 

NO HEAT.

Plug unit into grounded outlet, wait 3 to 5

 

minutes

and check to

 

see that the heater

 is

 not

 

operating. If

operating,

 

disconnect power and check

 

for improper

wiring. If

 

no

t

 operating then turn

 

thermostats to

highest

 

position and wait 3 to 5

 

minutes. Check to

see that

 the

OPERATING INSTRUCTIONS 

Unit or Series 

       SAVE THESE INSTRUCTIONS 

heater 

is

 operating. Should 

it

 not be

 

operating,

disconnect power and check wiring. 

2. Allow entire system to operate steadily for 1/2 hour.

This should remove oily residue from manufacturing.

(Some smoking may occur

 from element

).

3. Select the setting for comfort

 or your job requirement

.

4.

A safety limit control is provided to turn off the

 

heater 

elements 

automatically if it is blocked or 

otherwise

 

overheats due to an abnormal condition.

 

DO NOT

 

bypass or remove this safety 

limiting 

device 

from the

 

electrical circuit. During normal use, this 

safety

 

control should not operate. If you find that 

this

 

control is operating, make sure the heater is not

 

being blocked

 or filte

r is

 plugged

. If it continues to

 

cycle the heater

 

elements 

off, disconnect power to 

heater and

 

have it checked

 

and repaired by a 

qualified

 

electrician.

Table 

1

Troubleshooting Chart for Electric Heaters 

SYMPTOM 

PROBLEM 

SOLUTION 

Breaker Trips 

1. Short Circuit
2. Overloaded Circuit
3. Improper Voltage

1.

Find source of short. Trace heater circuit and verify the heater is wire properly.

2.

Reduce wattage in circuit. Refer to circuit sizing table for maximum wattage.

3.

Verify the heater voltage matches the supply voltage.

Heater not working  1.

No Power

2.

Loose Connections

3.

Defective Limit

1. Turn Breaker ON, turn thermostat ON, check that the breaker is position

properly on panel bus-bar. A 2-Pole breaker must be connected to both bus-
bars (A&B phase) to produce 240V power.

2. Tighten wire connections.
3. By-pass the limit to test. If heater works, replace the limit.

Heater Smokes 

1.

Oil on Element

2.

Needs Cleaning

1. It is normal for the element to burn off some light finishing oil used in the

manufacturing process when first energized. Open windows and allow room
to vent until it stops, usually within a few minutes.

2. Remove any dust or dirt accumulations.

Room Temperature 
does not match 
thermostat setting 

1. Thermostat affected

by another heat
source.

2. Improper calibration

1.

Sunlight or other heat sources can affect the thermostat. Move the thermo

stat to another location or remove the heat source. 

2.

Remove cover and adjust calibration screw.

Room Temperature 
swings from too hot 
to too cold 

1. Defective or low

quality thermostat

1.

Replace with a better quality thermostat. Anticipated thermostats are fair-

ly accurate; an electronic thermostat is best. 

Отзывы: