_________________________________________________________________________________________
Page 10 of 15 King Pigeon Communication Co.,Limited. Ver 1.5 File No.:RTU5025103
A Professional GSM 3G M2M products manufacturer
and automation solution provider, since 2005.
www.GSM-Gate-Opener.com [email protected]
6.0 Start ( this step is MUST):
Send to the RTU5025 for adjust the time.
6.1 Change Password
RTU5025 return: “Password changed to“new password”, please remember it carefully.”if sucessfully.
E.g.:
1234P666
for change the new password to 6666.
6.2 Authorized number managerment
6.2.0 Add authorized number:
A:
command code.
serial number:
the authorized
number’s position.
start time:
yy(year)mm(month)dd(day)hh(hour)mm(minute).the start time of this number can call in to control.
end time:
yy(year)mm(month)dd(day)hh(hour)mm(minute).the end time of this number can call in to control.
Without start time and end time means: Always can call in to control.
E.g.:
1234A003#123456#
to set the phone no.123456 at the 3
rd
position and always can call in to control.
E.g.:
1234A016#123456#1502050800#1502051000#
to set the phone number 123456 at the 16
th
position,
this number can call in to control during Feb 5
th
8:00a.m.(1502050800) to Feb 5
th
10:00a.m.(1502051000).
Note:
1. The authorized number means the one who can dial the RTU5025 to control the relay.
2. The Serial Number is the position to store the authorized users, from 001~999.
3. The 1
st
~6
th
position number should be Mobile number because of the alarm message will send to these
6 numbers, and the power failure alarm SMS send to the 1
st
postion number only.
6.2.1 Inquiry the Authorized number
’s position(serial):
E.g.:
1234A002#
to check the number on the 2
nd
position(serial number2).
6.2.2 Inquiry batch users number
E.g.:
1234AL002#050#
to inquiry the authorized numbers from the 2
nd
to the 50
th
,RTU5025 return serval
SMS with the numbers list(10 numbers on each SMS).
6.2.3
Delete the Authorized Number
(
or you can overwrite this postion with another number).
E.g.:
1234A002##
to delete the 2
nd
authorized number.
pwdAserial number##
!
1234Pnew password
pwdAserial number#authorized number#start time#end time#
pwdAserial number#
pwdTELphone number of the RTU5025#
pwdALserial number start#serial number end#
!