Page
58 of 76
King Pigeon Communication Co., Ltd.
V1.0
www.iot-solution.com
Modbus to MQTT IoT Gateway
-BL101
to change LAN port IP address according to requirement. IP Address change will not
be effective until gateway is power off and powered on again
5.2.1.5 Add LAN Port Device S475
(1) Click LAN and right click mouse to enter device configuration box
(2) Device Name: input the name of device to be added, S475
(3) Device IP: input S475 IP address. For example, S475 is set to auto retrieving IP.
Open S475 configuration software and view its IP(192.168.3.125). Thus input
S475 IP 192.168.3.125.
(4) Device Port: input LAN port device port. For example, S475 Modbus TCP port is
502. Thus put 502
(5) Device Brand: Modbus; Device Model: Modbus TCP
(BL101 collects S475 through LAN port through Modbus TCP protocol)
(6) Station ID: 1, (S475 Modbus ID is 1)
(7) Select Data Type. For example, S475 power source and temperature & humidity
data is 16-bit AB type, 32-bit data is not collected. Thus select 16-bit AB type and
keep 32-bit data type with default setting
(8) Click OK to confirm the setting
Note: S475 device icon will appear after confirming the configuration. If more
devicesto be added, perform the same procdure as Step (1)-(8)
Note: Click Save Data and gateway will restart automatically. After restarting, device
S475 is added successfully