ELECTRICAL REQUIREMENTS &
MAGNETIC SWITCH OPERATION
POWER SUPPLY
WARNING:
THIS CABINET SAW CAME PRE-WIRED FOR 220V
OPERATION AND MUST BE CONNECTED TO AN APPROPRIATELY
GROUNDED 220V OUTLET AS SHOWN IN FIG.1.
GROUNDING
WARNING:
IF OUTLET IS NOT PROPERLY GROUNDED, THIS
CABINET SAW CAN CAUSE ELECTRICAL SHOCK, PARTICULARLY
WHEN USED IN DAMP LOCATIONS. TO AVOID SHOCK OR FIRE,
IF THE POWER CORD IS WORN OR DAMAGED IN ANY WAY, HAVE
IT REPLACED IMMEDIATELY.
Not all outlets are properly grounded. If you are not sure if your outlet
is properly grounded, have it checked by a qualified electrician.
This cabinet saw must be grounded, if it should malfunction or
breakdown, grounding provides a path of least resistance for electric
current, which reduces the risk of electric shock.
WARNING:
TO MAINTAIN PROPER GROUNDING OF YOUR TABLE
SAW, DO NOT REMOVE OR ALTER THE GROUNDING PRONG IN
ANY MANNER.
EXTENSION CORDS
The use of any extension cord will cause some loss of power. Use the
following table to determine the minimum wire size (A.W.G-American
Wire Gauge) extension cord you will need. Use only 3-wire extension
cords which have 3-prong grounding type plugs and 3-hole
receptacles which accept the tool’s plug.
For circuits that are further away from the electrical circuit box, the wire
size must be increased proportionately in order to deliver ample
voltage to the cabinet saw motor. Refer to Fig.2 for wire length and
size.
MAGNETIC SAFETY SWITCH OPERATION
The magnetic safety switch as shown in Fig.3 needs to be installed to
underside of the front rail, see assembly section in this manual for
further instructions.
Do not turn the cabinet saw on until all assembly and adjustment
instructions have been done.
To start the cabinet saw, press the green start button (A) Fig.3 and to
stop the cabinet saw, press the red emergency stop button (B).
WARNING!
ALL ELECTRICAL CONNECTIONS MUST BE DONE BY A QUALIFIED ELECTRICIAN. FAILURE TO COMPLY MAY RESULT IN
SERIOUS INJURY! ALL ADJUSTMENTS OR REPAIRS MUST BE DONE WITH THE MACHINE DISCONNECTED FROM THE
POWER SOURCE. FAILURE TO COMPLY MAY RESULT IN SERIOUS INJURY!
FIGURE 1
PROPERLY
GROUNDED OUTLET
CURRENT CARRYING
PRONGS
GROUNDING
PRONG
FIGURE 3
LENGTH OF
EXTENSION CORD
0-25 FEET
26-50 FEET
51-100 FEET
WIRE SIZES REQUIRED
(AMERICAN WIRE GAUGE)
220V LINES ONLY
NO.12
NO.12
NO.10
FIGURE 2