„Zurück“- Taste

● Auswahl eine Ebene zurück

● Bedienerebene durch mehrmaliges Drücken erreichbar 

● Bricht Eingabevorgang ab

„OK“- Taste

● Auswahl eine Ebene vorwärts

● Wechsel in das Parametereingabefeld

● Bestätigung der Eingabe

„Grüne“- Taste

Dauerhaft grünes Licht

● Signalisiert, dass Verdichter läuft

● Blinkt zusammen mit „Rot“-Taste: Frequenzumrichter

   befindet sich im Konfigurationsmodus

FS 4.7

www.frigokimo.com

Ensure that all recommendations for compliance to mounting, electrical safety, EMC and UL regulations have 

been adhered to.

1. Basic information on first set-up

1.1 Recommendations

  

It is important to ensure that an interlocked contactor is fitted between the Refrigeration Inverter and the

   compressor if a parallel bypass connection is used.

 

In particular ensure that two isolated contacts of a relay are connected to the Safe-Torque-Off inputs of  

F

rigo

P

ack

®

 

FU+ 

Refrigeration Inverter: STO-A (Terminal X10:1) / STO-B (Terminal X10.3).

•  Remove start command (cable to terminal X13:2)

•  Connect main power supply

1.2 Keypad functionality

1.3 Menus - Selection of user level for first set-up

To start commissioning, the user level TECHNICIAN must be enabled. Please follow the steps shown below. 

Press key "Back" several times to access the menu "View Level".  

Password for user level TECHNICIAN: 

8670

. The level is then activated for 10 minutes.

- 2 -

OK

OK

OK

OK

PASSWORD:

8670

Back

Back

Start screen

Menu levels 

User level

Key "Back"

● Navigates to previous level

● Press multiple times to enter Operator Menu

● Aborts the edit mode

Key "OK"

● Displays the next menu level

● Changes to parameter entry mode

● Accepts value entered

"Green" key

Green light on

● Compressor running

● When flashing with "Red" key: Frequency Inverter 

    in Configuration Mode

Key "Red"

● Resets any trip

Red light on

● Compressor stopped

● When flashing with "Green" key: Frequency Inverter 

    in Configuration Mode

Keys "Left" and "Right"

● Displays previous menu level

● Selects the digit to be changed

Keys "Up" and "Down"

● Moves up or down through selected menu level

● Increments / decrements the value of the displayed  

    parameter by "1"