1. Introduction

DBM610 airflow meter allows 

control and balancing

 of airflow in air conditioning system. 

Thanks to the interchangeable 

hoods

, the airflow can be used on any type of grids or diffusers in air supply or exhaust.

Easy to handle, lightweight, it allows 

accurate, sturdy and fast measurements

.

It is supplied in standard with a 

610 x 610 mm

 hood. Four other dimensions are available as options:

1020 x 1020 mm

720 x 720 mm

720 x 1320 mm

420 x 1520 mm

These hoods are airtight and have a transparent part on each side, allowing the user to see through the vent and 

ensure that the hood is in a good position. The rods, made of fibreglass, provide a sturdiness of hoods.

The measurement grid, attached to the base, allows the measurement through 

48 points

 all over the surface of the

grid. Measurement is performed using a 

differential pressure sensor

, calibrated and compensated in atmospheric 

pressure and temperature.

The measuring unit of the airflow meter, removable, can be used as a micromanometer.

Real addition to airflow measurement, this instrument allows, by connecting a Pitot tube, to measure airflow velocity in air 
duct or, by connecting two silicone tubes, to check filter fouling of air station. It is also possible to connect the matrix grid 
designed for air velocity measurements on any types of large celling vent or diffuser. This grid calculates the average air 
velocity from 24 points to guarantee a reliable measurement.

1.1. Key points

Measuring range from 

40 to 3500 m

3

/h

Quick and simple 

hood changes

Software for data processing on computer (datalogger 10)

Sturdy, lightweight and easy to handle

Removable 

measuring unit

Interchangeable 

hoods

1.2. Technical features

Airflow: 

Measuring range: 

from 40 to +3500 m

3

/h

Accuracy: 

3% of measuring ±10 m

3

/h

Resolution: 

1 m

3

/h

Air velocity: 

Measuring range: 

from 0.2 to 10 m/s

Accuracy: 

3% of measuring ±0.04 m/s

Resolution:

 0.01 m/s up to 3 m/s and 0.1 m/s beyond

Temperature (on the base)

Measuring range: 

from 0 to 50°C

Accuracy: 

2% of measuring ±0.1°C

Resolution: 

0.1°C

Thermocouple Temperature (on the micromanometer)

Thermocouple type: 

K, J, T, S

Measuring range: 

K: from -200 to 1300°C 

J: from -100 to 750°C
T: from -200 àto400°C
S: from 0 to 1760°C

4

Introduction

Содержание DBM610

Страница 1: ...DBM610 AIRFLOW METER ...

Страница 2: ......

Страница 3: ...icromanometer mode 14 5 1 Starting up 14 5 2 Set the micromanometer 14 5 2 1 Select the airflow sensor 14 5 2 2 Set the surface 14 5 2 3 Set measurement units 15 5 2 4 Set a damping 15 5 2 5 Activate or deactivate the solenoid valve 15 5 2 6 Set the thermocouple type 15 5 2 7 Set the compensation temperature 16 5 2 8 Activate or deactivate the standardised airflow 16 5 3 Activate or deactivate air...

Страница 4: ...r Real addition to airflow measurement this instrument allows by connecting a Pitot tube to measure airflow velocity in air duct or by connecting two silicone tubes to check filter fouling of air station It is also possible to connect the matrix grid designed for air velocity measurements on any types of large celling vent or diffuser This grid calculates the average air velocity from 24 points to...

Страница 5: ...ctors Ø 7 x 4 mm Storage capacity 200 datasets of 100 points Housing Shock proof made of ABS IP54 protection Keypad 12 keys Conformity Electromagnetical compatibility NF EN 61326 1 guideline Power supply 4 alkaline batteries LR6 Rechargeable battery Li ion 3 7 V 4400 mhA optional Environment Neutral gases Operating temperature From 0 to 60 C Storage temperature From 20 to 70 C Auto shut off Adjust...

Страница 6: ...ion of airflow meter Carrying handle Protective cover Location for the electronic housing Integrated ergonomic handle Button of point point measurement start Electronic card Silicone tube for pressure routing Receipt cup hood rods Measurement grid Temperature probe Two pressure connectors ...

Страница 7: ... LCD 86 x 51 mm Auto shut off adjustable from 0 to 120 min Manual or automatic autozero Removable housing for micromanometer function 4 magnets at the back allow the mounting on the base airflow meter mode 2 pressure plugs allow to set the housing on the base and the connection of silicone tube for the measurement with a Pitot tube 1 thermocouple plug on the top of the housing micromanometer mode ...

Страница 8: ...6 1 5V Rechargeable batteries and Li Ion battery are available as options To replace batteries rechargeable or not Remove the batteries cover then used batteries Disconnect the batteries support Replace batteries then reconnect the support Replace the batteries cover To put the Li Ion battery optional Remove the batteries cover then the batteries support Connect the battery Replace the batteries c...

Страница 9: ...rs numbered from 1 to 8 are stuck on each end of the elements Example with 720 x 720 mm frame Mounting the airflow meter 9 Transparent mica allowing a good visibility and making easy the position of the hood Elastic to hold the hood on the base Frame with a foam to ensure a good airtight with ceiling Frame rods Step 1 Cloth of the hood 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 ...

Страница 10: ...ame Proceed the same way for the rest of the cloth When the cloth is fixed on the frame Place the cloth on the base The mark on the cloth and the Velcro tape are opposed to the carrying handle of the base Put the elastic of the cloth around the DBM base Tighten the Velcro tape of the cloth on the base If necessary turn the cloth to match the mark of the cloth with the mark on the base 10 Mounting ...

Страница 11: ...corner of the holding cup The crossing rods must be on the same plan as the KIMO logo Proceed the same way for the three other rods For the 1020 x 1020 mm 1320 x 720 mm and 1520 x 420 mm length frames the plastic supple protections on the hood must be positioned in front of the cups on the frame Mounting the airflow meter 11 Rounded end in the holding cup Rounded end in the holding cup Flat end in...

Страница 12: ...lect the required correction coefficient with up and down arrows then press OK Screen displays the selected coefficient It is possible to modify it with arrow keys Press OK to validate and back to Configuration menu 4 2 2 Set measurement units Go to Unit line then press OK Go to the required line airflow temperature or pressure then press OK Select unit with up and down arrows then press OK Availa...

Страница 13: ...automatic averages Results of the aggregate of averages are based on several datasets of automatic average it means that the DBM 610 should not be turn off and the Esc key should not be pressed Once a 1st dataset of automatic average has been realized and saved Press OK or the red button on the right of the base to go to measurement screen Press OK again or the red button on the right of the base ...

Страница 14: ...dard airflow allows to activate or not the standardized airflow as per DIN1343 standard 5 2 1 Select the airflow sensor Go to Airflow sensor line then press OK Press OK on the Element line Select the airflow sensor Pitot tube L Pitot tube S Debimo blade Matrix grid or Coefficient with up arrow and down arrow then press OK It is also possible to select the corresponding coefficient to the airflow s...

Страница 15: ...alculate the volumetric flow rate Qv K ΔP Go to Surface then press OK Go to K factor line then press OK Select the K factor with up and down arrows then press OK If necessary modify the value of K factor with arrows then press OK if no modification just press OK Press Esc to quit Surface sub menu and back to Configuration menu 5 2 3 Set measurement units Go to Units line then press OK Go to the re...

Страница 16: ... cm 3 x 15 cm 3 x 25 cm These struts allow to remain parallel to the celling The length of the struts allow to be more or less distant from the celling it can be useful in case of high air velocity Indeed the air velocity decreases as soon as we keep away from the celling vent To connect the silicone tubes Ensure that each silicone tube is connected correctly For example the white one connected on...

Страница 17: ...of the 1st point The device displays measurements and the remaining measurement duration Press OK to add measurement points Press Moy Avg button to get to screen results when the required number measurement points has been reached Press up and down arrows to get to results of different parameters Press Save to save dataset or Esc to cancel and back to measurement screen 5 6 Perform an autozero The...

Страница 18: ... required dataset then press OK Dataset opens with following features Number of points Dataset type Date and time of beginning and end Press OK to display values Values table opens Use left and right arrows to change of page Use up and down arrows to change parameters Press Esc to back to the recorded dataset list 6 2 Delete recorded datasets Press Delete line then press OK A message is displayed ...

Страница 19: ...automatic shut off Go to Extinction line then press OK Select OFF to deactivate it or the time before automatic shut off 15 30 45 min or 1h Press OK to validate 7 4 Set brightness Go to Brightness line then press OK Select the required level of brightness from 1 to 9 or AUTO with up and down arrows Press OK to validate 7 5 Set contrast Go to Contrast line then press OK Select the required level of...

Страница 20: ...cation then press OK Screen displays software version number and device serial number Press Esc to back to Informations menu 8 2 Calibration Go to Calibration then press OK Screen displays calibration date of the device Press Esc to back to Informations menu 8 3 After sales service Go to After sales service then press OK Screen displays Kimo after sales services phone number and email Press Esc to...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...ntractual document We reserve the right to modify the characteristics of our products without prior notice Once returned to KIMO required waste collection will be assured in the respect of the environment in accordance to 2002 96 CE guidelines relating to WEEE ...

Отзывы: