Centauri Energy Server
–
User Manual Model Number -GF-80000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
40
4. Switch ON the RECTIFIER and BYPASS switches of the Energy Sever.
5. Switch ON the switches of
“
PV n #
”
in turn.
6. Press the
“
INV ON
”
button on the panel to confirm the dialogue information of the touch screen to
boot the Energy Server.
Touch operation:
Click the
“
”
button
on the main interface and then select the “Boot”
option
and click “OK” button
.
7. Switch ON the output switch.
5.1.3 Power OFF Steps:
1. Press the
“
INV OFF
”
button on the panel to confirm the dialogue information of the touch screen.
Touch operation:
Click the
“
”
button “OFF” button and “
OK
”
button in turn, the system will switch
OFF the Energy Server.
2. Switch OFF the output switch.
3. Switch OFF the switches of
“
PV n#
”
in turn.
4. Switch OFF the RECTIFIER and BYPASS switches of the Energy Sever.
5. Switch OFF the DC START switch of the Energy Sever.
6. Switch OFF the RECTIFIER and BYPASS input switches of the external power of the Energy Sever.
7. Switch OFF the switches of the battery.
5.1.4
Power ON Procedures (Parallel system):
1.
Make sure that all parallel cables are connected properly, and the total output of the parallel
system is disconnected from the load.
2.
Turn ON
the output switch, “BYPASS” switch and “DC START” switch of all
Energy Severs in the
parallel system.
3.
Turn ON the Energy Sever
1 “RECTIFIER” switch and press the
Energy Sever
1 “ON” button to
power ON. The REC indicator starts blinking, and after about 15 seconds, the BYP green indicator
is OFF, the INV green indicator is steady ON and the Energy Sever starts to output via the inverter,
Note:
If the panel requires a power-on password, please contact the after-sales staff.