Sirius Capacitor Module
–
User Manual
Model Number -7100-48-B-2C-M-SD-A-FL
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
24
Warning Messages
Description
Trouble Shooting
Over-Current (OC)
OC occurs when the current
goes above 500A or when
the
module
is
short-
circuited. In this event, the
protected terminal will
shut down.
Switch off the circuit breaker and
check the continuity across the
module terminals to find whether
there is a short circuit. In case of a
short circuit, check the operating
circuitry and clear the short circuit.
Over-Temperature (OT)
OT
occurs
when
the
module temperature goes
above 80°C. In this event,
the protected
terminal
turns off.
Shut down the Module and check
the surrounding temperature and
ensure the ambient temperature is
less than 80°C. If not leave the
Module to cool till the Module
temperature comes below 80°C.
Now, turn ON the circuit breaker.
Please Remove Charger/ Please
Connect Charger
This happens when there is
some residual current. In
this event, the Module
gives alarm for full charge
or low charge and the
charger/discharger is also
disconnected
but
the
protected terminals are not
activated.
In SiriusVIEW application, select
SiriusConfig then go to Calibrate
Zero Current. Press Calibrate. If you
see “No load curre
nt is set
successfully”, it means the current
is set to zero.
11.
Features
11.1 Key Features
•
Low power consumption.
•
Accurate SOC estimation.
•
Cell balancing.
•
Detection of circuit board errors.
•
Long service life.
11.2
Physical features
•
Sirius module is easy and secure to operate with Anderson Connectors.
•
SSR (Solid State Relay) is used to control terminals in Sirius module. SSR has more life
than AC or DC contactors and responds faster than any control methods.
•
Sirius Module has embedded safety functionality in the event of:
•
High Cell Voltage
•
Low Cell Voltage
•
High Terminal Voltage
•
Low Terminal Voltage
•
High Terminal Current
•
High Ambient Temperature