Kilowatt Labs 7100-48-B-3.3C-M-SD-A-FL Скачать руководство пользователя страница 24

 

Sirius Capacitor Module 

 User Manual  

 

Model Number -7100-48-B-2C-M-SD-A-FL 

This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.

  

Kilowatt Labs, Inc. 

www.kilowattlabs.com

 

 

   24 

 

 

Warning Messages 

Description 

Trouble Shooting 

Over-Current (OC) 

OC occurs when the current 
goes  above  500A  or  when 
the 

module 

is 

short-

circuited. In this event, the 
protected  terminal  will 
shut down. 

Switch  off  the  circuit  breaker  and 
check  the  continuity  across  the 
module  terminals  to  find  whether 
there is a short circuit. In case of a 
short  circuit,  check  the  operating 
circuitry and clear the short circuit. 

Over-Temperature (OT) 

OT 

occurs 

when 

the 

module  temperature  goes 
above  80°C.  In  this  event, 
the  protected 

terminal 

turns off. 

Shut  down  the  Module  and  check 
the  surrounding  temperature  and 
ensure the ambient temperature is 
less  than  80°C.  If  not  leave  the 
Module  to  cool  till  the  Module 
temperature  comes  below  80°C. 
Now, turn ON the circuit breaker. 

Please Remove Charger/ Please 
Connect Charger 

This happens when there is 
some  residual  current.  In 
this  event,  the  Module 
gives  alarm  for  full  charge 
or  low  charge  and  the 
charger/discharger  is  also 
disconnected 

but 

the 

protected terminals are not 
activated. 

In  SiriusVIEW  application,  select 
SiriusConfig  then  go  to  Calibrate 
Zero Current. Press Calibrate. If you 

see  “No  load  curre

nt  is  set 

successfully”,  it  means  the  current 

is set to zero. 

 

11.

 

Features 

11.1  Key Features 

 

Low power consumption. 

 

Accurate SOC estimation. 

 

Cell balancing. 

 

Detection of circuit board errors. 

 

Long service life. 

11.2

 

Physical features 

 

Sirius module is easy and secure to operate with Anderson Connectors. 

 

SSR (Solid State Relay) is used to control terminals in Sirius module. SSR has more life 
than AC or DC contactors and responds faster than any control methods. 

 

Sirius Module has embedded safety functionality in the event of: 

 

High Cell Voltage 

 

Low Cell Voltage 

 

High Terminal Voltage 

 

Low Terminal Voltage 

 

High Terminal Current 

 

High Ambient Temperature 

Содержание 7100-48-B-3.3C-M-SD-A-FL

Страница 1: ...SIRIUS CAPACITOR MODULE User Manual Model number 7100 48 B 3 3C M SD A FL Version 1 0 Release Date May 2019...

Страница 2: ...att Labs Inc Kilowatt or the Company Specifications in this Manual are subject to change without notice While every attempt has been made to make the Manual accurate and up to date users are cautioned...

Страница 3: ...ppearance 7 3 2 2 Mechanical Drawings 7 3 2 3 Dimension and Weight 9 3 3 Front Panel Description 9 4 Module Installation 13 4 1 Inspection 13 4 2 Safety Gear 14 4 3 Unpacking and Contents Check 14 5 O...

Страница 4: ...ions for unpacking mounting installation and operation of a Sirius module Please read this manual carefully before operating the system and follow all warnings and safety instructions to prevent accid...

Страница 5: ...mstances o Do not connect or disconnect terminals from the Module without first disconnecting the load o Do not touch the terminals with conductors while the Module is charged Serious burns shock or m...

Страница 6: ...ped to you either by air or by sea If you receive the Modules shipped by air please follow the instructions given below Carefully remove the nails from all the four sides of the wooden box and open it...

Страница 7: ...A FL This manual is subject to change without notice and at the sole discretion of Kilowatt Labs Inc Kilowatt Labs Inc www kilowattlabs com 7 3 2 Product Overview 3 2 1 Appearance The appearance of th...

Страница 8: ...le User Manual Model Number 7100 48 B 2C M SD A FL This manual is subject to change without notice and at the sole discretion of Kilowatt Labs Inc Kilowatt Labs Inc www kilowattlabs com 8 Top View Sid...

Страница 9: ...cription 1 Circuit Breaker C100A Circuit Breaker 2 2 Fault Reset Fault Reset Button 3 LCD 16 2 LCD 4 Aux Auxiliary USB 5 Comm Connector Communication Connector USB 6 Comm Status Communication Status L...

Страница 10: ...and Instantaneous Power e Press the Fault Reset button to see the individual cell voltages Checking for individual Cell Voltage When the fault reset button is pressed the LCD after displaying the stat...

Страница 11: ...the LCD displays the following message it means that cell balancing has been disabled Step 5 To make the current zero follow the steps below When the current is not zero the LCD will display the follo...

Страница 12: ...ched ON from the circuit breaker the Module gets power and the LCD shows the following message after 3seconds under normal operation After 1 second the following two LCD screens gets switched between...

Страница 13: ...ON The protected terminal is active Green OFF The protected terminal is not active 7 Protected Terminal This is the output terminal of the module which has electronic switch protection that is limited...

Страница 14: ...equirements of the end use application Installation must be performed by professional installers only Switch off the system and check for hazardous voltages before altering any connection Sirius modul...

Страница 15: ...ction of Cables to Anderson Connectors First connect the Anderson Connector to the Cables of the Module by following the steps below Take Anderson Connector as shown in the picture Strip the insulatio...

Страница 16: ...nc www kilowattlabs com 16 Hold the housing and place the connector into the back of the housing and push it tightly Make sure the Anderson connector is firmly hooked Step 2 Connecting the Load Connec...

Страница 17: ...ble to see the terminal status LED OFF 4 Wait till the LCD screen on the Module displays initial values 5 Press and hold the fault reset button after 3 seconds the terminal status LED will change to G...

Страница 18: ...nication andmonitoring 3 Turn on the Sirius module by pressing the fault reset button 4 Wait till the LCD screen on the Module displays initial values 5 Double click on the SiriusVIEW application to e...

Страница 19: ...Recovery Procedure When the Module voltage drops below a certain threshold the control electronics are turned OFF To restart the control electronics follow the steps below 1 Use the Unprotected termi...

Страница 20: ...ed Voltage 44V 54V 8 Connecting the Modules in Parallel or in Series The capacity or voltage of the Modules can be increased by connecting them in parallel or series respectively 8 1 Parallel Connecti...

Страница 21: ...l Modules Take out the output positive and output negative from the respective commonpoint 8 2 Series Connection of Sirius Modules A maximum of 8 modules can be connected in series with a Module Combi...

Страница 22: ...st module and Output Negative from the last module 9 Automatic Safety Shutdown The Module will automatically shut down under any excessive use conditions in order to prevent damage to the itself and c...

Страница 23: ...Module reaches the minimum voltage and it is in standby mode the LCD will display this message every 30 seconds When the Module has reached the minimum voltage and the Module is connected to a load t...

Страница 24: ...the Module temperature comes below 80 C Now turn ON thecircuit breaker Please Remove Charger Please Connect Charger This happens when there is some residual current In this event the Module gives alar...

Страница 25: ...dule like Communication LED Red Blinking while communicating Terminal LED Green Active while terminal is ON Inactive while terminal is OFF 11 3 Technical Features Sirius Module has one processor for a...

Страница 26: ...www kilowattlabs com 26 Internal SD card reading refreshing Statistical Analyzing Graphical results 12 Shelf Life Shelf life is the life of the Module in years from the date it is manufactured to the...

Отзывы: