40 of 56
Revision 4
KiloVault
®
LLC • 330 Codman Hill Road, Boxborough, MA 01719 • +1 (888) 218-5924 •
• www.kilovault.com
Device
Setting
Under 40A
Charger
40-60A
Charger
60-150A
Charger
Maximum
Charge Rate
1C
Recharge /
Rebulk Volts
Set to start charging from solar before
charging by AC (just above the
inverter/charger's recharge/rebulk voltage of
51.4 V).
Battery
Monitor
Midpoint Sensor
If you are using a battery monitor with
midpoint sensors, secure the midpoint sensor
leads out of the way and electrically isolate
the midpoint sensors with electrical tape,
shrink wrap, or any other appropriate
method.
Midpoint sensors are only used on strings of
batteries in series. Since KiloVault® HAB™ V4
units are
NEVER
connected in series, midpoint
sensors are not used.
Battery
Temperature
Sensor
Do not use an external battery temperature
sensor with these batteries.
Battery
Temperature
Compensation
If the sensor is required for the battery
monitor to work, set the battery temperature
compensation to 0mV / °C
5.3.1.
Firmware Updates
•
Ensure that your KiloVault® HAB™ V4 is connected to the internet and
added into KiloVault® HAB™ V4 iT (the KiloVault® HAB™ V4 mobile
application).
•
Ensure your WiFi router and internet connection are not using power
from your inverter. You do not want these devices to lose power during
the update.
•
If your KiloVault® HAB™ V4 is using the scheduled charging feature,
temporarily disable scheduled charging.
•
On the KiloVault® HAB™ V4 iT Basic screen flip the slider-like switch
highlighted in blue shown in Figure 20: KiloVault® HAB™ V4 iT Basic