7.2 Environmental
7.3 Physical
2022
29
Specification
Value
Ambient Temperature Range
-4°F to 113°F (-20° C to 45°C)
Optimal Internal Temperature Range
59°F – 95°F (15 – 35°C)
Internal Temperature Range - Charging
32°F to 113°F (0°C to 45°C)
Internal Temperature Range - Discharging
-4°F to 131°F (-20°C to 55°C)
High Internal Temperature Charge Protection
149°F (65°C) with protection release at 122°F (50°C)
High Internal Temperature Discharge Protection
149°F (65°C) with protection release at 122°F (50°C)
Low Internal Temperature Charge Protection
32°F (0°C) with protection release at 39°F (4°C)
Low Internal Temperature Discharge Protection
-4°F (-20°C) with protection release at 14°F (-10°C) )
Ingress Protection - Water
Please see section 8, Certifications
Splashing Water: Water splashing against the enclosure
from any direction shall have no harmful effect.
Maximum Altitude
3000 meters
Recommended Humidity
45% to 75%
Specification
Value
1200 HLX+ Height
9.25 ± 0.08 in (235 ± 2 mm)
1200 HLX+ Width
6.5 ± 0.08 in (165 ± 2 mm)
1200 HLX+ Length
12.52 ± 0.08 in (318 ± 2 mm)
1200 HLX+ Weight
25.8 lb (11.7 kg)
2400 HLX+ Height
10.04 ± 0.08 in (255.2 ± 2 mm)
2400 HLX+ Width
6.8 ± 0.08 in (172.5 ± 2 mm)