background image

11

n

 

1500 W type

n

 

Specifications

Item/Model

PWX1500L

PWX1500ML

AC input

Nominal input rating

100 Vac to 240 Vac, 50 Hz to 60 Hz, single phase

Input voltage range

85 Vac to 265 Vac

Input frequency range

47 Hz to 63 Hz

Current (MAX) 

*1

100 Vac

21 A

200 Vac

10.5 A

Inrush current (MAX) 

*2

75 Apeak or less

Power (MAX) 

*3

2200 VA

Power factor (TYP) 

*1

0.99 (input voltage 100 V), 0.97 (input voltage 200 V)

Efficiency (MIN) 

*1

74 % or more

Hold-up time for power 

interruption (MIN) 

*3

20 ms or greater

*1. 

With rated load. 

*2. 

Excludes the charge current component that flows through the 

capacitor of the internal EMC filter circuit immediately after the POWER switch is turned on (for 

approximately 1 ms). 

*3. 

100 Vac with rated load.

Item/Model

PWX1500L

PWX1500ML

Output

Rating

Output voltage 

*1

30 V

80 V

Output current

 *1

 

150 A

56 A

Output power

1500 W

Voltage

Setting range

0 V to 31.5 V

0 V to 84 V

Setting accuracy

± (0.05 % of set +0.05 % of rating)

Line regulation 

*2

± 5 mV

± 10 mV

Load regulation 

*3

± 5 mV

± 10 mV

Transient response 

*4

1 ms or less

Ripple noise 

*5

(p-p) 

*6

 60 mV

 80 mV

(rms) 

*7

8 mV

Rise time

Rated load

100 ms

No load

100 ms

Fall time

Rated load

100 ms

No load

800 ms

Maximum remote sensing

compensation voltage (single line)

1.5 V

4 V

Temperature coefficient (MAX) 

*8

100 ppm/°C (during external control)

Current

Setting range

0 A to 157.5 A

0 A to 58.8 A

Setting accuracy

± (0.5 % of set +0.1 % of rating)

Line regulation

± 17 mA

± 7.6 mA

Load regulation

± 35 mA

± 16.2 mA

Ripple noise 

*9

(rms) 

*7

300 mA

130 mA

Temperature coefficient (TYP) 

*8

100 ppm/°C

*1. 

The maximum output voltage and current are limited by the maximum output power. 

*2. 

85 Vac 

to 135 Vac or 170 Vac to 265 Vac, fixed load. 

*3. 

The amount of change that occurs when the load is 

changed from no load to rated load (rated output power/rated output voltage) with rated output voltage. 

The value is measured at the sensing point. 

*4. 

The amount of time required for the output voltage to 

return to a value within “rated output voltage ± (0.1 % +10 mV).” The load current fluctuation is 50 % to 

100 % of the maximum current with the set output voltage. 

*5. 

Measured using an RC-9131 1:1 probe 

that conforms to the JEITA specifications. At the rated output current.  

*6. 

When the measurement 

frequency bandwidth is 10 Hz to 20 MHz. 

*7. 

When the measurement frequency bandwidth is 5 Hz to 

1 MHz. 

*8. 

When the ambient temperature is within 0 °C and 50 °C. 

*9. 

When the output voltage (Rated 

Power ÷ Rated Current)  is 10 % to 100 % of the rating. At the rated output current. 

Display function

Voltage display

Maximum display

99.99 (fixed decimal point)

Display accuracy 

± (0.2 % of r5 digits)

Current display

Maximum display L: 999.9 (fixed decimal point), ML: 99.99 (fixed decimal point)
Display accuracy 

± (0.5 % of r5 digits)

Power

display

 *1

The PWR DSPL key lights in red.

Maximum display

9999

Display accuracy  Displays the result of multiplying the current and voltage

Operation display

OUTPUT ON/OFF, CV operation, CC operation,

Alarm operation, Remote operation (LAN operation),

Key lock operation, Preset memory

*1. 

Press PWR DSPL to display the power on the ammeter. Each time you press this key, the 

display switches between power and current.

Protection functions

Overvoltage protection (OVP), Overvoltage protection 2 (OVP2), Overcurrent protection 

(OCP), Undervoltage limit (UVL), Overheat protection (OHP), Overheat protection 2 (OHP2), 

Fan failure protection (FAN), Incorrect sensing connection protection (SENSE), Low AC input 

protection (AC-FAIL), Shutdown (SD),  Power limit (POWER LIMIT)

Signal output

Monitor signal 

output 

*1

Voltage monitor (VMON) Selectable monitor voltage range: 0 V to 5 V or 0 V to 10 V

Setting accuracy

2.5 % of f.s.

Current monitor (IMON) Selectable monitor voltage range: 0 V to 5 V or 0 V to 10 V

Setting accuracy

2.5 % of f.s.

Status signal 

output 

*1*2

OUTON STATUS, CV STATUS, CC STATUS,

ALM STATUS, PWR ON STATUS

*1. 

J1 connector on the rear panel. 

*2. 

Photocoupler open collector output; maximum voltage 30 

V, maximum current (sink) 8 mA; isolated from the output and control circuits; status commons are 

floating (withstand voltage of less than or equal to 60 V); and status signals are not mutually isolated.

Control features

External

control

*1

Output voltage

control (VPGM) 

0 % to 100 % of the rated output voltage

Selectable control voltage range: 0 V to 5 V or 0 V to 10 V

Accuracy

5 % of f.s.

Output current

control (IPGM)

0 % to 100 % of the rated output current

Selectable control voltage range: 0 V to 5 V or 0 V to 10 V

Accuracy

5 % of f.s.

Output on/off control

[OUTPUT ON/OFF CONT]

Possible logic selections: turn the output on using a low TTL

level signal or turn the output on using a high TTL level signal

Output shutdown control

[SHUT DOWN]

Turns the output off with a low TTL level signal

Alarm clear control

[ALM CLR]

Clears alarms with a low TTL level signal

*1.

 J1 connector on the rear panel

Other features

Master-slave parallel operation

Including the master unit, up to four units

(all the same model) can be connected.

Series operation

Up to two units (all the same model) can be connected.

Preset memory

Up to three sets of the following settings can be saved: the set 

voltage, the set current, the set OVP, the set OCP, and the set UVL.

Key lock

Locks the operation of all keys other than the OUTPUT key.

Interface

Software protocol

IEEE Std 488.2-1992

Command language

Complies with SCPI Specification 1999.0

Has a compatibility mode (switchable)

l  

Genesys Series made by TDK-Lambda

 

N5700/N8700 made by Agilent Technologies

 

PAG Series made by Kikusui

RS232C, USB, LAN

USBTMC-USB488, LXI 1.3 Class C

*1. 

Option 

*2. 

Only on models that have the CE marking on the panel. Does not apply to specially 

ordered or modified PWXs. 

*3. 

This is a Class I equipment. Be sure to ground this product’s 

protective conductor terminal. The safety of this product is only guaranteed when the product 

is properly grounded. 

*4.

 This is a Class A equipment. This product is intended for use in an 

industrial environment. This product may cause interference if used in residential areas. Such use 

must be avoided unless the user takes special measures to reduce electromagnetic emissions 

to prevent interference to the reception of radio and television broadcasts. 

*5.

 This is a Group 1 

equipment. This product does not generate and/or use intentionally radio-frequency energy, in 

the form of electromagnetic radiation, inductive and/or capacitive coupling, for the treatment of 

material or inspection/analysis purpose.

Item/Model

PWX1500L

PWX1500ML

General

Environmental 

conditions

Operating

environment

Indoor use, overvoltage category II

Operating

temperature/humidity

0 ℃ to +50 °C/20 %rh to 85 %rh (no condensation)

Storage

temperature/humidity

-10 °C to +60 °C/90 %rh or less (no condensation)

Altitude

Up to 2000 m

Cooling method

Forced air cooling using fan

Grounding polarity

Negative grounding or positive grounding possible

Isolation

voltage

± 250 Vmax

Isolated analog 

interface 

*1

± 60 Vmax

Withstand 

voltage

Input-FG

No abnormalities at 1500 Vac for 1 minute

Input-Output

No abnormalities at 2000 Vac for 1 minute

Output-FG

No abnormalities at 1500 Vdc for 1 minute

Input-Isolated 

analog interface 

*1

No abnormalities at 2650 Vac for 1 minute

Output-Isolated 

analog interface 

*1

No abnormalities at 2300 Vdc for 1 minute

Insulation 

resistance

500 Vdc, 100 MΩ or more

Output-FG

500 Vdc, 40 MΩ or more

Safety 

*2

Complies with the requirements of the following directive and standard.

Low Voltage Directive 2006/95/EC

EN 61010-1 (Class I 

*3

, Pollution degree 2)

Electromagnetic

compatibility (EMC) 

*2

Complies with the requirements of the following directive and standard.

EMC Directive 2004/108/EC

EN 61326-1 (Class A 

*4

), EN 55011 (Class A 

*4

, Group 1 

*5

EN 61000-3-2, EN 61000-3-3

Applicable under the following conditions

The maximum length of all cabling and wiring connected to the PWX 

Series must be less than 3 m.

Dimensions (maximum)/Weight

485 W×43(44) H×500(580) Dmm/Approx. 9.5 kg

Accessories

Output terminal cover: 1 pc., Input terminal cover set, Output 

terminal M8 bolt set: M8 bolts ×2 sets(Bolt, nut, spring washer, 

and washer for each bolt), Chassis connection wire: 1 wire, 

J1 connector plug kit: 1 set(Housing: 1 pc., Connector: 1 pc., 

Plug: 1 pc., Strain relief: 1 pc., Clips: 2 pcs., and two types of 

Screws: 2 pcs.,), Packing list: 1 copy, Quick reference (1 each 

for English and Japanese), Safety precautions: 1 copy, China 

RoHS sheet: 1 copy, CD-ROM: 1 disc

PWX series

Thin & Wide range

* A power cord is not included. Please purchase the optional 

accessory separately (AC5.5-3P3M-M4C-VCTF).

Содержание PWX Series

Страница 1: ...ght design with 1U height for increased rack mounting efficiency Voltage and current range can be varied within the rated power the ratio of 3 times Rated output power 750 W 1500 W Rated output voltag...

Страница 2: ...2 A Next Generation Rack Mounted Power Supply 1U Multi Range Programmable DC Power Supply Thin Wide range DC Power Supply PWX series Ideal for N to M network based remote control and monitoring...

Страница 3: ...re essential for system upgrades The series also has a virtual multi channel bus VMCB function that allows it to be used efficiently for remote control and monitoring with 1 to N and as well as with N...

Страница 4: ...can be set and the maximum number of units can be configured up to 31 units per group A group can have a mixture of models The PWX series is equipped with LAN USB and RS232C interfaces as standard fea...

Страница 5: ...r s device Furthermore the RS232C interface corresponds to other products by setting the command language into a LGCy language Emulation setting Command language setting function n Application Softwar...

Страница 6: ...ted by setting the bleeder circuit to OFF state It is possible to omit the diode for reverse current prevention required for the charge of such a battery l A startup state setup at the time of output...

Страница 7: ...master slave parallel operation 9 PRL COMP IN Correction signal input terminal for master slave parallel operation 10 A COM External signal common for pins 5 to 9 11 to 13 20 to 22 24 and 25 During r...

Страница 8: ...alf independent packaging KRA1 PWX HALF SINGLE Rack mount adapter for 1U half interconnected packaging KRA1 PWX HALF PAIR 1500 W model AC power cord 3 m AC5 5 3P3M M4C VCTF Isolated analog interface f...

Страница 9: ...key has an LED SHIFT key Used to enable the functions that are written in blue characters below the key VOLTAGE knob Used to set the voltage value or change the value of a CONFIG parameter Air inlet l...

Страница 10: ...ge control VPGM 0 to 100 of the rated output voltage Selectable control voltage range 0 V to 5 V or 0 V to 10 V Accuracy 5 of f s Output current control IPGM 0 to 100 of the rated output current Selec...

Страница 11: ...ernal control 1 Output voltage control VPGM 0 to 100 of the rated output voltage Selectable control voltage range 0 V to 5 V or 0 V to 10 V Accuracy 5 of f s Output current control IPGM 0 to 100 of th...

Страница 12: ...duct Model Remark AC power cord for PWX750ML AC2 3P3M IEC320 UL For Japan and U S with plug total length 3 m rated voltage 125 V rated current 15 A AC1 3P2R5M IEC320 EU For Europe with plug total leng...

Отзывы: