4-20
PAT-T 4kW
CF27 Breaker trip setting when the shutdown signal is applied
Sets whether to trip the breaker (turn the POWER switch off) when an external
shutdown (SD) signal is applied. The setting is possible even when the product is
used as a slave unit.
CF28 Breaker trip setting when the OVP or OCP is activated
Sets whether to trip the breaker (turn the POWER switch off) when the overvoltage
protection (OVP) or overcurrent protection (OCP) is activated. The setting is
possible even when the product is used as a slave unit.
CF29 Voltage limit setting
Sets whether to limit the output voltage setting so that it does not exceed the
overvoltage protection setting (to approximately 95% of the OVP trip point) Cannot
be set when the output is on.
CF30 Current limit setting
Sets whether to limit the output current setting so that it does not exceed the
overcurrent protection setting (to approximately 95% of the OCP trip point) Cannot
be set when the output is on.
See
Settings
Description
oFF
N
ot trip (t
u
rn the o
u
tp
u
t off) (factory defa
u
lt)
on
Trip (t
u
rn the POWER s
w
itch off)
See
Settings
Description
oFF
N
ot trip (t
u
rn the o
u
tp
u
t off) (factory defa
u
lt)
on
Trip (t
u
rn the POWER s
w
itch off)
See
Settings
Description
oFF
N
ot limit (factory defa
u
lt)
on
Limit
See
Settings
Description
oFF
N
ot limit (factory defa
u
lt)
on
Limit
Содержание PAT160-25T
Страница 17: ...General Description This chapter describes an overview and describes the features...
Страница 22: ...1 6 PAT T 4kW...
Страница 34: ...2 12 PAT T 4kW...
Страница 73: ...External Control This chapter describes external analog control and remote monitoring using the J1 connector...
Страница 106: ...6 12 PAT T 4kW...
Страница 158: ...7 52 PAT T 4KW...
Страница 159: ...Maintenance This chapter describes maintenance such as cleaning inspecting and calibrating...
Страница 171: ...Specifications This chapter describes the specifications and gives the dimensions of the PAT...