Product Description

SBM51/11

Datasheet 2.50-40.151-11-EN

Issue 2014-11-19

Phase menu L2

DDC3000: M090 SBM51 Gateway
DDC4000: CD_SB51

NOTE

Due to rounding errors caused by scaling, the values of the parameters 2212, 2251, 2215 and 2252 
in the DCC may differ from the display on the device (last digit).

Parameter 
name

Parameter plain text Parameters provided

Operating mode L2

Unit

2209

External building com-
plex malfunction

Participant is logged in

2210

Analog actual value 1 Delta voltage U23

 V

2211

Analog actual value 2 Phase voltage U2

 V

2212

Analog actual value 3 Total reactive energy (inductive / incoming high rate) (k) VArh

2251

Analog actual value 4 Total reactive energy (inductive / incoming low rate) (k) VArh

2215

Analog actual value 5 Total reactive energy (capacitive / outgoing high 

rate)

(k) VArh

2252

Analog actual value 6 Total reactive energy (capacitive / outgoing low rate) (k) VArh

2253

Analog actual value 7 Phase current I2

 A

2254

Analog actual value 8 Effective power P2

(k) W

2255

Analog actual value 9 Apparent power S2

(k) VAr

2256

Analog actual value 10 Idle power Q2

(k) VA

2257

Analog actual value 11 Power factor cos 

φ

2224

Digital actual value 2

2212, 2251, 2215, 2252
0 – inductive / capacitive
1 – incoming / outgoing

2225

Digital actual value 3

0 – high rate / 1 – low rate

2217

Operating mode

Device present - 'Automatic'
Device not found - invalid

Содержание SBM51/11

Страница 1: ...220 and A230 A230s with communication module EMMOD 201 from the company Camille Bauer Application The switch cabinet bus module SBM51 11 is used to integrate up to 8 energy monitoring devices into the...

Страница 2: ...to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with t...

Страница 3: ...tors and controls 2 LEDs in housing 2 rotary switches in housing for setting the switch cabinet bus address Interfaces Switch cabinet bus to DDC system Serial interface RS485 bus Modbus RTU Overvoltag...

Страница 4: ...the switch cabinet bus also applies to the CAN bus Switch cabinet bus When connecting the switch cabinet bus use a cable of at least type JY St Y 2x2x0 8 Lg two x two leads stranded into a pair plast...

Страница 5: ...m cable length for the Modbus is 1000 m The SBM51 11 uses the following interface parameters Baud rate 9600 baud Data bits 8 Stop bit 1 Parity even The energy monitoring devices must use the same sett...

Страница 6: ...of the DDC controller is described in the respective project planning documentation Indicators and Controls 1 Rotary switch for setting the switch cabinet bus address 2 Switch cabinet bus LED LED Sign...

Страница 7: ...tting the switch cabinet bus address are located inside the SBM51 11 Set the first rotary switch to the first digit of the switch cabinet bus address and the second rotary switch to the second digit T...

Страница 8: ...eter 2204 Foreign bus OK Parameter 2204 reports malfunctions on Modbus to the SBM51 11 1 Modbus is working without errors 0 Errors occurred on Modbus Parameter List in the DDC4000 System Enable parame...

Страница 9: ...0 A230s Parameter 2220 totals menu Set display of performance values parameters 2254 2255 2256 Parameter 2220 sets the display of the performance values for parameters 2254 2255 2256 within the softwa...

Страница 10: ...the digital input on the energy monitoring device The rate that currently applies is displayed in parameter 2225 totals menu If the digital input on the energy monitoring device is used for changing...

Страница 11: ...value 1 Delta voltage U12 V 2211 Analog actual value 2 Phase voltage U1 V 2212 Analog actual value 3 Total energy incoming high rate k Wh 2251 Analog actual value 4 Total energy incoming low rate k Wh...

Страница 12: ...lue 3 Total reactive energy inductive incoming high rate k VArh 2251 Analog actual value 4 Total reactive energy inductive incoming low rate k VArh 2215 Analog actual value 5 Total reactive energy cap...

Страница 13: ...er name Parameter plain text Parameters provided Operating mode L1 L2 L3 Unit 2209 External building com plex malfunction Participant is logged in 2210 Analog actual value 1 Module type 2211 Analog ac...

Страница 14: ...deleted or 0 off 1 on 2220 Q digital setpoint 2 Factor for display Power unit 2245 Q digital setpoint 3 Factor for display Energy unit 2246 Q digital setpoint 4 0 high rate 1 low rate 2217 Operating m...

Страница 15: ...t Present 2251 Total power incoming low rate Present Present Present 2215 Total power outgoing high rate Present Present Present 2252 Total power outgoing low rate Present Present Present 2253 Phase c...

Страница 16: ...Present 2255 Apparent power S3 Present 2256 Idle power Q3 Present 2257 Power factor cos 3 Present Par no Measured quantity Single phase 3W balanced load 4W balanced load 3W unbalanced load 4W unbalanc...

Отзывы: