A
Page 5 / 32
Datasheet 1.10-65.040-01-EN
RPW414P-FTL
Product Description
Issue 2017-04-10
Item
Technical Data
RPW414P-FTL Room control module with room humidity/temperature sensor, SolarRadio technol-
ogy and integrated bidirectional EnOcean wireless interface.
Automatic determination of the utilization time profile/heating profile in the room for
automatic control of comfort mode and economy mode.
For self-learning, energy self-sufficient and occupation-dependent control of the
room temperature in conjunction with MD15-FTL wireless small actuator.
Nominal voltage
Dual power supply consisting of a solar cell and an internal energy stor-
age unit with priority management
Additional internal energy source 2x 3.6 V, AA lithium
Measured quantity
Room temperature and relative humidity in homes and offices
Measuring system
Temperature sensor:
Occupancy sensor:
Humidity sensor:
- Integrated digital measuring transducer
- Integrated PIR (“Passive infrared”) sensor
- Integrated digital measuring transducer
Measuring range
Temperature:
Relative air humidity:
0..50 °C
20..80%
Measuring tolerance
Temperature:
Relative air humidity:
Typically ±0.3 K
Typically ±3.0%
Display
LCD display:
■
Room temperature, room humidity, date or time, as required
■
Status indicators
Controls
■
Occupancy button: manually switch between comfort mode/
economy mode
■
Up arrow button: increase value
■
Down arrow button: reduce value
■
Selector button: select the menus or displays
Interfaces
EnOcean® radio interface:
■
Radiogram: EnOcean radiogram, bidirectional
■
Frequency: 868.3 MHz
■
Duty cycle: < 1%
■
Cyclic transmission/reception intervals
Communication cycle
10 min
Transmission power
< 10 mW
Illumination strength
Min. 150 lux recommended
Operating range
Radio:
Occupancy sen-
sor:
Approx. 30 m in buildings (depending on building
structure)
Approx. 10 m
Housing
Plastic housing, RAL 9010 (pure white), 7001
Other colors on request
Protection class
III
Degree of protection
IP30
Ambient temperature
0..50 °C
Ambient humidity
During operation: 20..85% r.h., non-condensing
Out of operation: 5..90% r.h., non-condensing