A
Page 10 / 12
Product Description
RBW301-C, RBW302-C, RBW304-C, RBW305-C
Datasheet 1.10-60.010-01-EN
Issue 2017-07-20
Temporarily extending the room utilization time (RBW302-x, RBW305-x)
Requirement: The timer is set but is not active (outside of room utilization time).
►
Switch the presence button to “Present”.
The utilization time extension is displayed as a timer.
►
Rotate the knob: The utilization time can be extended by up to four hours (from the set time).
The new utilization time extension is displayed as a timer.
Setting the time
►
Press and hold the knob for three seconds.
►
Rotate the knob: Select the TIME function. Press the knob: Confirm selection.
►
Set the time:
Set the hour. Confirm the setting.
Set the minute. Confirm the setting.
►
Set the date:
Set the year. Confirm the setting.
Set the month. Confirm the setting.
Set the day. Confirm the setting.
The settings for the time and date are applied. The display changes back to the standby
display.
CAN Address Setting
The address switch (1) is located on the PCB of the room control module (rear of device).
Address setting:
■
For RCN150-L, RCN151-L, RCN152-L, RCN155-L, RCC200-L or RCN200-L with basic appli-
cation: Address 1 for main room,
Address 2 for secondary room
■
For RCN150-L, RCN151-L, RCN152-L, RCN155-L, RCC200-L, RCN200-L or RCN420-B
configured with PS4000: Address 1 to 4 for room 1 to 4
■
DDC4000: Address 1 to 9
■
DDC420: Address 1 to 9
1
Adressschalter
1