Technical data sheet  1.15-10.002-01-en

 

Multi radio connection MFA

 

D e v i ce   De s c ri p ti on

 

 
 

Initial operation

 

LED displays

 

 

LED

 

Function

 

 

 off

 

MFA receives no radio telegrams

 

 

 

green short blinking

 

passive operating mode; module receives radio telegrams of other 
transmission paths

 

 

 

green long blinking

 

 

 

(LED approx 1 s 
on)

 

active service mode; module receives radio telegrams of the 
assigned transmitters (FCS)

 

 

 

red permanent light

 

error mode:

 

 

 

 

 

Failure of the radio communication

 

 

 

 

Output signal 30 % (security position servo drive)

 

 

 

 

 

 

 

 

 

 

 

The error blinking of the LED continues as long as the 
state causing the error remains

 

 

 

 

 

 

 

  

Warning

 

 

 

 
 

Description of initial operation

 

 
1. Before switching on the mains, check the correct assembly and electric connection.

 

 

Initial operation may be performed only by qualified expert personnel!

 

 
 
 

 

 Note

 

Specific settings and functions of the MFC are described in this device description. Additionally to 
this notice, the device documentation MFC and FCS are to be noted.

 

 
 

 

Set the address code

 

 
 

The same address code must be set at the assigned transmitting modules as well.

 

 

 

The device is delivered with the setting “000”.

 

 Warning

 

 

 
 

 

Training with the MFA and the corresponding field device takes place automatically with the first regularly 
received radio telegram.

 

 
 

 

Please observe possibly delayed data transmission due to the transmission interval of a radio path!

 

 Note

 

 

 

 

 

Radio communication in the 868 MHz frequency band is not maintained permanently, but is subject 
to a legally determined relationship between transmission period and transmission pause ("duty 
cycle").

 

 
 
 
 

 

When the radio communication is interrupted, the connected drives are set in a security position. 
The valves are then opened to 30%.

 

 Note

 

 

 

 

 

The reception of a valid radio telegram resets this function. 
The red error LED at the FCE turns off.

 

 

 

Page 8 / 8

 

Содержание Multi radio connection MFA

Страница 1: ...ly Contents Notes on the device description Page 2 Safety Instructions Page 2 Qualified specialists Page 2 Application Page 3 Type Page 3 Technical data Page 3 Assembly Page 4 Installation Page 6 Connection Page 6 Addressing Page 6 Initial operation Page 8 Kieback Peter GmbH Co KG Tempelhofer Weg 50 D 12347 Berlin Telephone 49 0 30 600 95 0 Telefax 49 0 30 600 95 164 E Mail info kieback peter de h...

Страница 2: ... carried out by qualified specialists see paragraph Qualified specialists Every person utilizing the devices shall have read and understood the descriptions in the technical data sheet Meaning of the symbols in the technical data sheet Warning of dangerous electrical voltage Danger General warning strictly observe this notice Warning Further notice to observe Note Danger means mortal danger severe...

Страница 3: ...us small servo drives of the types M25Y or M15Y S2 MFA Type MFA Multi radio connection as a radio converter for the indirect wireless activation of up to two wire connected continuous small servo drives With integrated switching power supply 230 V AC 24 V DC Technical data Primary mains 230 V AC 10 12 VA Secondary mains 24 V AC 15 7 VA Received frequency 868 35 MHz Analog output 0 10 V DC 5 mA Deg...

Страница 4: ...rials and screening elements e g installation shafts fire doors switching cabinet doors etc must already be taken into account during the planning phase High humidity increases the natural signal attenuation Warning Recommendation Plan the radio paths horizontally on one level with max 30 m distance between transmitting and receiving components Note Observe the minimum distances to potential sourc...

Страница 5: ...he cable entry Cable inlet for assembly with flush mounted box Cable inlet for surface mounted installation application of the hood for wall mounting 1 Release safety screw and take off hood Hood inserts as extra item 2 Cable inlet from the back breakout 5mm 60 M3 x 20 60 M3 5 x 45 Cable inlet from below After the housing lead through of the cable provide a traction relief Warning 3 Wire MFA accor...

Страница 6: ...ection diagram or the applicable appliance connection scheme Connection MFA Use only small servo drives with DC power supply Note Addressing In the housing the MFA has 3 rotary switches for setting the system code and the device address By means of the 3 digit address code radio paths can be established with theoretically up to 999 participants Terminals small servo drives Service key multi colore...

Страница 7: ... 10 V Adr 01 0 MFA Adr 01 0 Setting the address code The 3 digit address code consists of a 1 digit system code and a 2 digit device address Example for address 23 1 Device address 23 0 1 2 3 4 5 6 7 8 9 x1 x10 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 Device address System code System code 1 Via the system code participants of a radio network can be grouped according to different criteria e g floor...

Страница 8: ... Specific settings and functions of the MFC are described in this device description Additionally to this notice the device documentation MFC and FCS are to be noted Set the address code The same address code must be set at the assigned transmitting modules as well The device is delivered with the setting 000 Warning Training with the MFA and the corresponding field device takes place automaticall...

Отзывы: