A
Page 9 / 10
Datasheet 2.50-40.132-01-EN
FBG132-FTL EnOcean System Gateway
Product Description
Issue 2013-08-13
Commissioning
!
NOTICE
Commissioning by switching on the supply voltage may occur only after the commissioning
technician/engineer has finished configuring the DDC and has set the fieldbus address.
■
Configuration is described in the project planning documentation for the DDC4000 automation
station.
■
The DDC4000 automation station is configured and commissioned using the PS4000 planning
system. You can find more information in the PS4000 manual.
NOTE
A button cannot be used for teaching in on the FBG132-FTL. The radio ID of the radio partner is
entered into the configuration parameters in the PS4000 planning system.
The radio ID is specified on the devices’ type plates.
NOTE
- A total of 16 FBG132-FTL units can be connected per DDC4000 automation station.
- The maximum number of radio units per DDC4000 automation station is 512.
Teaching in radio partners
■
Unidirectional communication
►
Enter the radio ID and device type into the project planning.
►
Commission the FBG132-FTL.
■
Bidirectional communication
►
Enter the radio ID and device type into the project planning.
►
Commission the FBG132-FTL.
►
Trigger a teach-in signal on the radio partner.