CAN bus installation notes
Lines for the mains supply and fieldbus are to be laid together in one shielded cable, cable type at
least 0.8 mm in diameter, with the wires twisted together in pairs. Here, one stranded pair of wires is
to be used for the mains supply and the other for the fieldbus.
At the end of the fieldbus (furthest point from the DDC controller, max. 2000 m), the two connection
lines must be fitted with a terminating resistor of about 180 ohm (terminating resistor is included with
the DDC controller).