A
Page 9 / 10
Datasheet 3.50-32.016-01-EN
DSY/4..32
Product Description
Issue 2011-05-04
Rotational angle limitation DSY/8..32
The maximum working range (rotational angle) of actuating drives DSY/8..32 is 90° (delivery setting).
The adapter can be reinserted if the rotational angle needs to be limited.
Setting Example
Proceed as follows to limit the rotational range to 0°to 60° from 0° to 90°:
(1) Adapter
Set actuator to 90° rotational angle for end
position.
Disengage the adapter’s retaining clips (1) on
the underside of the actuator and pull out the
adapter (1) to the front of the unit.
Re-insert the adapter (1) in the new end posi-
tion of 60° rotational angle.
Push in the adapter (1) in the new 60° end posi-
tion until the retaining clip locks in place again.
1
1
2
3
4