A
Page 8 / 10
Product Description
DSY/4..32
Datasheet 3.50-32.016-01-EN
Issue 2011-05-04
Adjusters O and S
The Y control signal is preset to 0 to 10 V (Y1) and 0 to 20 mA (Y2) (adjuster O = 0, adjuster S = 10).
Using both adjusters O (starting point) and S (working range), the input of the Y control signal can be
changed.
Double switch A
Switch 1
can be used to adjust control signal Y to the mechanical rotational angle of DSY/8..32
(automatic adaptation, on = ON position).
When the switch is set to ON, the actuating drive performs a single initialization run. With the initial-
ization run, both end positions are approached automatically.
ON position: When control signal Y is changed or the rotational angle is automatically limited, control
signal Y is adjusted to the available rotational angle.
Delivery setting: Off (for 0 to 10 V, 0 to 20 mA, and 0 to 90° rotational angle).
Switch 2
is used for reversing the rotational direction.
Delivery setting: 0 to 10 V or 0 to 20 mA = right rotational angle, 0° ->90°.
For exam-
ple, for
Y1= 2..10 V
Adjuster
O
= 2
Adjuster
S
= 8
and
Y2= 4..20 mA Adjuster
O
= 2
Adjuster
S
= 8
Double switch A (1)
Double switch A (2)
Without adaptation
With adaptation
Rotational direction to
the right
Rotational direction
to the left
1 2
ON
OFF
1 2
ON
ON
1 2
ON
0°
(0V)
90°
(10V)
1 2
ON
0°
90°
(10V)
(0V)