Product Description
BMR410
Datasheet 2.70-10.411-01-EN
Issue 2011-04-27
Fieldbus Power Supply
In the simplest case, the fieldbus module can be supplied with power from the BMR410.
When JY(St)Y 2x2x0.8 Lg bus cables are used, the following maximum fieldbus lengths are possible:
Tab. 1: Maximum fieldbus length per power supply
By installing additional power supplies, you can use a fieldbus length of up to 2000 m.
■
Fieldbus Power Supply: DC 12 V; 6 W
NOTE
The
BMF
does not require any additional power supplies as it is supplied over the cascade plug and
not from the fieldbus.
NOTE
FBS
modules always need to be supplied with external power as they require an AC 24 V power
supply (the power supply for the fieldbus is DC 12 V). Therefore, the fieldbus length is not limited for
FBS modules.
FBU and FBM modules
DDC110 modules
Maximum fieldbus length
3
0 to 3
20 m
2
0 to 3
40 m
1
0 to 3
80 m
0
0 to 3
160 m
0 to 3 < 2 m
0 to 3
160 m