Specifications
Operating voltage
15.20 to 19.95 VDC
Current
Normal
operating
Alarm
43 uA
70 uA
Actual alarm point
129 to 141°F (53.9 to 60.6°C)
Vibration level
10 to 35 Hz, with an amplitude of
0.01 in.
Air velocity [1]
0 to 4,000 ft./min (0 to 20.32 m/s)
Rate-of-rise 15°F/min
(8°C/min)
Wall mount distance from
ceiling
12 in. (305 mm) max.
Maximum spacing [2]
for Heat Detectors
50 ft. (15.2 m) centers
Compatible bases
Standard
Relay
Isolator
Audible
KI-SB, KI-SB4
KI-RB, KI-RB4
KI-IB, KI-IB4
KI-ABDT, KI-ABLT
Compatible detector testers [3] Testifire 2000
Operating environment
Temperature
Relative
humidity
32 to 100°F (0 to 38°C)
0 to 90% noncondensing
Storage temperature
−
4 to 140°F (
−
20 to 60°C)
Environmental compensation
Automatic
[1] For duct installation, use a KI-DMP duct detector mounting plate
and install per P/N 3102482-EN.
[2] When replacing KI-HFD and KI-HRD detectors with the KIR-
OSHCD, ensure that the spacing is 50 ft. (15.2 m) or less.
[3] Requires the SIGA2-TSTSPACER Testifire adapter assembly.
Regulatory information
UL smoke
sensitivity range
0.5 to 4.36 %/ft. (1.63 to 13.62 %/m) obscuration
UL fixed-
temperature alarm
rating
135°F (57.2°C)
UL CO alarm level
UL CO False
alarm level
70 ppm 60 to 240 minutes [1]
150 ppm 10 to 50 minutes [1]
400 ppm 4 to 15 minutes [1]
30 ppm 30 days[1]
70 ppm 60 minutes[1]
North American
standards
UL 268-7, UL 521, UL 2075
Note: This detector has been evaluated to the CO
alarm sensitivity limits of UL 2034.
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
[1] Sensitivity per UL 2034