background image

 

P/N 3102527-

EN • REV 001 • ISS 14SEP18 

 

3 / 4 

Installation 

Notes 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to room 
temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector during 
installation and be removed prior to commissioning and service. 
The dust cover is not a substitute for removing the detector during 
new construction or heavy remodeling. 

• 

Do not install detectors until after final construction cleanup (unless 
otherwise specified by the AHJ). 

• 

Install per NFPA 720 

Standard for the Installation of Carbon 

Monoxide (CO) Detection and Warning Equipment

, UL 2075 

Standard for Gas and Vapor Detectors and Sensors

, and 

applicable codes. 

To install the detector: 

1.  Install and wire the base as described on the installation sheet 

supplied with the base. 

2.  Set the detector address.  Refer to the panel technical reference 

manual for a list of valid addresses.  Use a screwdriver to adjust 
the two rotary switches on the back of the detector.   
(See Figure 3:)  Set the left rotary switch (0 through 12) for the 10s 
and 100s digit and the right rotary switch for the 0 through 9 digit. 

3.  Attach the detector to the base by rotating the detector clockwise 

until it snaps into the locked position. 

4.  If required by the AHJ or local codes, affix the supplied CO 

Warning Label (P/N 3303928) in proximity to the detector. 

Figure 3: Setting detector address (address 52 shown) 

 

 

 

 

 
 
(1) Insert a screwdriver here to set the address 

Testing 

Before testing, notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

Test each sensor in the detector.  

Note: 

If the CO sensor is programmed as an alarm point, it must 

comply with the requirements of NFPA 720. 

To perform an initial installation test: 

1. 

Visually inspect each detector and verify that it is installed in the 
correct location.  Make sure that factors not apparent on the plans 
do not adversely affect the detector. 

2. 

Remove the detector from its base and verify that the proper 
detector address, trouble signals, and messages are reported. 

3. 

If wired for Class A operation, verify that the detector continues to 
operate first with SLC_IN disconnected, and then with SLC_OUT 
disconnected. (Refer to the installation sheet for the base.) 

4. 

Place a momentary ground fault on the SLC circuit and verify 
operation of the ground fault detection circuitry. 

5. 

Perform a sensor function test, as described below. 

To perform a CO sensor function test: 

1.  Use the fire alarm control panel to put the detector into accelerated 

response mode. (Refer to the panel technical reference manual for 
instructions.) 

2.  Activate the CO sensor using SDI LLC model Solo C6 CO aerosol 

spray without covering the head, or using the Testifire detector 
tester per the 

manufacturer’s instructions. 

Maintenance 

To ensure proper operation, plan maintenance (regular or selected) of 
the detector in accordance with the AHJ and all applicable governing 
laws, codes or standards. Refer to NFPA 720 

Standard for the 

Installation of Carbon Monoxide(CO) Detection and Warning 
Equipment

Refer to application bulletin  3102534-EN for additional information and 
cleaning instructions. 

CO sensor.

 The CO sensor has a 10 years life from the date of 

manufacture or when the control panel indicates a sensor end-of-life 
condition, whichever comes first. 

0

2

3

4

5

6

8

9

0

1

2

3

4

5 6 7 8

9

0

1

11

1

1

2

TENS

ONES

(1)

firealarmresources.com

Отзывы: