4 / 4
P/N 3102469-
EN • REV 003 • 04JUN18
Specifications
Operating voltage
15.20 to 19.95 VDC
Current
Normal operating
Alarm
51 µA
68 µA
Vibration level
10 to 35 Hz, with an amplitude of
0.01 in.
Wall mount distance from
ceiling
12 in. (305 mm) max.
Compatible bases
Standard
Relay
Isolator
Audible
KI-SB, KI-SB4, GSA-SB, GSA-SB4
KI-RB, KI-RB4, GSA-RB
KI-IB, KI-IB4, GSA-IB, GSA-IB4
KI-ABDT [1], KI-ABLT [1]
GSA-SBT [1]
Compatible detector testers
Testifire 2000
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 90% noncondensing
Storage temperature
−4 to 140°F (−20 to 60°C)
Environmental compensation
Automatic
[1] Required for those installations that must provide separate CO
(TC4) and fire (TC3) patterns from the sounder base. Refer to
GSA-T3T4 installation sheet p/n 3102073-EN.
Regulatory information
UL smoke
sensitivity range
0.53 to 3.94%/ft. (1.7 to 12.35 %/m) obscuration
UL CO alarm level
UL CO False
alarm level
70 ppm 60 to 240 minutes [1]
150 ppm 10 to 50 minutes [1]
400 ppm 4 to 15 minutes [1]
30 ppm 30 days[1]
70 ppm 60 minutes[1]
North American
standards
UL 268, UL 2075
Note: This detector has been evaluated to the CO
alarm sensitivity limits of UL 2034.
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
[1] Sensitivity per UL 2034
Contact information
For contact information, see www.kiddelifesafety.com.