background image

P/N 3102469-

EN • REV 003 • 04JUN18 

 

3 / 4 

The recommended CO detector locations are: 

• 

Outside each separate sleeping area in the immediate vicinity of 
the bedrooms (including areas such as hotel rooms and dorm 
rooms) 

• 

On every occupiable level of a dwelling unit, including basements, 
but excluding attics and crawl spaces 

• 

Centrally located on every habitable level of the building and in 
every HVAC zone based on an engineering evaluation considering 
potential sources and migration of carbon monoxide 

• 

On the ceiling in the same room as permanently installed fuel-
burning appliances 

• 

In any area required by local building codes, legislation, or the AHJ 

• 

In a suitable environment per the detector specifications (see 
““Specifications” on page 4 for details) 

• 

On a firm, permanent surface 

Do not install the CO detector: 

• 

Within 5 ft. (1.5 m) of any cooking appliance 

• 

Within 10 ft. (3 m) of a fuel-burning appliance 

• 

Near air conditioners, heating registers, or any other ventilation 
source that may interfere with CO gas entering the detector 

• 

Where furniture or draperies may obstruct the airflow 

• 

In a recessed area 

Figure 2: Recommended CO detector locations 

 

  Recommended CO detector location 

Testing 

Before testing, notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

Note: 

If the CO sensor is programmed as an alarm point, it must 

comply with the requirements of NFPA 720. 

To perform an initial installation test: 

1.  Visually inspect each detector and verify that it is installed in the 

correct location. Make sure that factors not apparent in the plans 
do not adversely affect the detector. 

2.  Remove the detector from its base and verify that the proper 

detector address, trouble signals, and messages are reported. 

3.  If wired for Class A operation, verify that the detector continues to 

operate first with SLC_IN disconnected, and then with SLC_OUT 
disconnected. (Refer to the installation sheet for the base.) 

4.  Place a momentary ground fault on the SLC circuit to verify 

operation of the ground fault detection circuitry. 

5.  Run a system detector sensitivity report on all detectors and verify 

that readings fall within acceptable limits. 

6.  Perform a sensor function test, as described below. 

To perform CO sensor function tests: 

1.  Use the fire alarm control panel to put the detector into accelerated 

response mode. (Refer to the panel technical reference manual for 
instructions.) 

2.  Activate the CO sensor using SDI LLC model Solo C6 CO aerosol 

spray without covering the head, or using the Testifire detector 
tester per the 

manufacturer’s instructions. 

To perform smoke sensor function tests: 

1.  If desired, use the fire alarm control panel to put the detector or 

zone into a service group for testing. (Refer to the panel technical 
reference manual for instructions.) 

2.  Activate the smoke sensor using No Climb Products model Smoke 

Centurion/M8, FireTech Smoke or Smoke Sabre smoke aerosol 
spray, a smoke generator, or the Testifire detector tester per the 
manufacturer’s instructions. 

Maintenance 

To ensure proper operation, plan maintenance (regular or selected) of 
the detector in accordance with the AHJ and all applicable governing 
laws, codes, or standards. Refer to NFPA 72 

National Fire Alarm and 

Signaling Code.

 NFPA 720 

Standard for the Installation of Carbon 

Monoxide (CO) Detection and Warning Equipment

Refer to application bulletin P/N 3102403-EN for additional information 
and cleaning instructions. 

CO sensor.

 The CO sensor has a 10 years life from the date of 

manufacture or when the control panel indicates a sensor end-of-life 
condition, whichever comes first. 

Отзывы: