P/N 3102469-

EN • REV 003 • 04JUN18 

 

KI-PCD Intelligent Photoelectric 
Smoke Detector with CO Sensor 
Installation Sheet 

 

Description 

The model KI-PCD Intelligent Photoelectric Smoke Detector with CO 
Sensor is an intelligent device that uses an optical sensing chamber to 
detect smoke, and a CO sensor to detect carbon monoxide from 

any

 

source of combustion. The detector analyzes the smoke and CO 
sensors independently to determine whether to initiate a fire alarm, a 
life safety CO alarm, or both. 

LED indicator. 

The LED indicator (see Figure 1) displays the following 

states: 

• 

Normal: Green LED indicator flashes, no action. 

• 

Alarm/active: Red LED indicator flashes, evacuate the area. 

Sensor end-of-life indicator: 

The detector signals a 

“COMMON TRBL ACT” condition on the control 

panel when the CO sensor reaches its end of life. Pressing the Details 
button 

on the control panel displays “END OF LIFE ACT” providing 

verification that it is an end-of-life trouble of the CO sensor. This 
trouble remains active until the detector is replaced, even if the panel is 
reset. 

 

Figure 1: KI-PCD features 

 

(1)  Self-locking tab 
(2)  LED indicator 

 

 

Installation 

Notes 

• 

This detector does not sense fires in areas where smoke cannot 
reach the detector. Smoke from fires in walls, roofs, or on the 
opposite side of closed doors may not reach the detector. 

• 

This detector does not detect oxygen levels or flames. Use this 
device as part of a broad-based life safety program which includes 
a variety of information sources pertaining to heat and smoke 
levels, extinguishment systems, visual and audible devices, and 
other safety measures. 

• 

Photoelectric detectors have a wide range of fire-sensing 
capabilities and are best suited for detecting slow, smoldering fires. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to room 
temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector during 
installation and be removed prior to commissioning and service. 
The dust cover is not a substitute for removing the detector during 
new construction or heavy remodeling. 

• 

Do not install detectors until after final construction cleanup (unless 
otherwise specified by the AHJ). 

• 

Do not use smoke detectors with detector guards unless the 
combination has been evaluated and found suitable. 

• 

Install per NFPA 72 

National Fire Alarm and Signaling Code

NFPA 720 

Standard for the Installation of Carbon Monoxide (CO) 

Detection and Warning Equipment

, and UL 2075 

Standard for Gas 

and Vapor Detectors and Sensors

• 

Upon completion of the original installation and following any 
modifications or additions to the system, perform a calibrated 
sensitivity test per NFPA code. The Signature Series can perform 
this test and generate a system sensitivity report. 

To install the detector: 

1.  Install and wire the base, as described on the installation sheet 

supplied with the base. 

2.  Remove the serial number label from the detector and attach it to 

the project documentation. 

3.  Attach the detector to the base by rotating the detector clockwise 

until it snaps into the locked position. 

4.  If required by the AHJ or local codes, affix the supplied CO 

Warning Label (P/N 3303928) in proximity to the detector. 