Architectural and Engineering

Specifications

 

The smoke alarm shall be Kidde Model i12060 or approved equal.  

It shall be powered by a 120VAC, 60Hz source along with a 9V battery 
backup. The unit shall incorporate an ionization sensor with nominal  
sensitivity of 0.50 to 1.06%/ft. The temperature operating range shall  
be between 40°F and 100°F (4°C and 38°C) and the humidity operating 
range shall be 5% - 95% relative humidity.
 

The smoke alarm can be installed on any standard single gang  

electrical box, up to a 4” octagon junction box. The electrical connection 
(to the alarm) shall be made with a plug-in connector. A maximum of 
24 Kidde devices can be interconnected in a multiple station arrange-
ment. The interconnect system must not exceed the NFPA (National Fire 
Protection Association) limit of 18 initiating devices, of which 12 can  
be smoke alarms. With 18 initiating devices (Smoke, heat, CO, etc),  
interconnected, it is still possible to interconnect 6 strobe lights and/or 
relay modules. The alarm shall provide optional tamper resistance that 
deters removal of the unit from the wall or ceiling and locks the battery 
door closed. No additional pieces shall be required to activate this feature.
 

The alarm shall include an easy access battery compartment that is 

opened and closed by pressing on the battery door. The 9V battery carrier 
will ensure proper battery backup protection by not allowing the battery 
door to close if the battery is placed in the unit incorrectly or if a battery 
is not present. The unit shall also provide an optional tamper resistant 
switch that will prevent the battery door from being opened.
 

The unit shall include a piezoelectric horn that is rated at 85  

decibels at 10 feet. The unit shall include the Smart Hush

TM

 feature  

that silences the unit for approximately 7 minutes if a nuisance  
condition occurs. 

The unit shall incorporate red and green LED indicators. The green  

LED (when illuminated) indicates the presence of AC power. The red LED 
(located under the TEST/Hush button) has 

four modes of operation:

Standby Condition:

 The red LED will flash every 30-40 seconds to  

indicate that the smoke alarm is operating properly. 

Alarm Condition:

  

When the alarm senses products of combustion and goes into alarm the 
red LED will flash one flash per second.  The flashing LED and pulsating 
alarm will continue until the air is cleared.When units are interconnected, 
only the red LED of the alarm that senses the smoke or is being tested 
(the originating unit) will flash.  All other units in the interconnected  
system will sound an alarm but their red LED’s will NOT flash. 

Alarm 

Memory:

  This smoke alarm is equipped with an alarm memory, which 

provides a visual indication when an alarm has been activated.  The red 
LED will illuminate for about 1.5 seconds every 16 seconds to indicate  
the memory condition. 

Smart Hush

TM

 Mode: 

 The red LED will illuminate 

for 1.5 seconds every 8 seconds, indicating the smoke alarm is in the  
Smart Hush

TM

 Mode. 

 

The unit shall at a minimum meet the requirements of UL217, 

NFPA72, and (chapter 11), The State of California Fire Marshall, NFPA101 
(0ne and two family dwellings), Federal Housing Authority (FHA), Housing 
and Urban Development (HUD).

120V AC/DC Wire-in Smoke Alarm

Front Battery Door

Part# 21006376

Model i12060

Technical Specifications

Model: 

i12060

Power Source: 

120VAC (

80mA), 

 60HZ, 9V battery backup

Audio Alarm: 

85dB at 10ft

Temperature Range:  40˚F to 100˚F (4˚C to38˚C)
Humidity Range: 

5%-95% relative humidity (RH)

Sensor: 

Ionization

Size: 

5” in diameter x 1.75” depth

Weight: 

.5lbs

Interconnects: 

Up to 24 Kidde devices

LED: 

Green, receiving AC power

 

Red, 4 modes of operation

Warranty: 

10 year limited warranty

Installation of Smoke Alarm

The smoke alarm should be installed to comply with all local codes having jurisdiction 
in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all 
alarms are wired to a single, continuous (non-switched) power line, which is not pro-
tected by a ground fault interrupter. A maximum of 1000 ft. of wire can be used in 
the interconnect system. Use standard UL listed household wire as required by code.

FUSE OR CIRCUIT BREAKER

BLACK

WHITE

RED

L

N

First 

Alarm

Additional 

Alarms

Ordering Information

Ordering  

 

 

 

Dimensions 

 

Case/ 

Layers/   

Skid  

Number 

UPC 

I2F5 

Pack Quantity 

(w x d x h inches)  Weight  Skid 

Skid 

Weight 

N/A 

7-84908-00135-1  N/A 

individual* 

5.75 x 1.5 x 5.75  0.5 lbs  N/A 

N/A 

N/A

21006376 

7-84908-00135-1  107-84908-00135-8 

Cut Case (6 units) 

6.5 x 13.25 x 6 

3 lbs 

147 

441 lbs

21005927 

0-47871-05927-0   200-47871-05927-4 

Bulk Pack (6 units) 

6 x 10.5 x 6 

3 lbs 

147 

441 lbs

21006932 

7-84908-00135-1  407-84908-00135-9 

Bulk Pack (36 units) 

19.5 x 11.75 x 12  18 lbs 

24 

432 lbs.

21006933 

7-84908-00135-1  307-84908-00135-2 

Display Pallet (36 units)  20 x 24 x 40 

20 lbs.  4 

90 lbs.

21005928 

0-47871-27689-9  100-47871-27689-6 

Cut Case (3 Twin Packs)  6.5 x 13.25 x 6 

3 lbs 

147 

441 lbs

Alk. Btry 21006931 

0-47871-27695-0  100-47871-27695-7 

Cut Case (6 units) 

6.5 x 13.25 x 6 

3 lbs 

147 

441 lbs

*Not for sale by individual unit

1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com

Distributed by:

P/N: KL-i12060 sheet 

rev. 01-2009