Stratos-Micra • INSTALLER’S HANDBOOK • Iss. 1
6
3.14 Remote Reset
–
Alarm actions
tab,
Remote input
subgroup
This function allows latching alarms or faults (see sections 3.17 and 3.18) to be
remotely reset when the relevant activating terminals are shorted together by volt-free
contacts.
When the function is enabled, entering a value of 01, 02 or 03 to the numeric field to
the left of the tick-box assigns the “I/P 1”, “I/P 2” or “I/P 3” terminals of a connected
relay/input card respectively as the activating terminals.
Remote terminals 4 and 5 are retained for future expansion.
Note: This function is only available via the optional Input/Relay Card. This board
is fitted in the same manner as an APIC card (see section 7.3). Only a single
expansion port is available, so an APIC card cannot be fitted at the same time as
an Input/Relay card.
3.15 Remote Day/Night
–
Alarm actions
tab,
Remote input
subgroup
This function allows the detector to be manually toggled between day and night opera-
tion
(see section 3.3.6)
when the relevant activating terminals are shorted together. It
is useful where the protected area is occupied at varying times, allowing the last person
to leave the area to activate the switch.
When the function is enabled, entering a value of 0 1, 02 or 03 to the numeric field to
the left of the tick-box assigns the “I/P 1”, “I/P 2” or “I/P 3” terminals of a connected
relay/input card respectively as the activating terminals.
Remote terminals 4 and 5 are retained for future expansion.
The day/night setting reverts to the previous state when the contacts are opened. The
function can be activated by a keyswitch, latching push button or any other device that
has volt-free short circuit contacts when activated. NB, enabling the function overrides
any day / night switch-over times previously set (see section 3.11).
Note: This function is only available via the optional Input/Relay Card. This board
is fitted in the same manner as an APIC card (see section 7.3). Only a single
expansion port is available, so an APIC card cannot be fitted at the same time as
an Input/Relay card.
3.16 Programmed Isolate
–
Alarm actions
tab
When this function is ticked the detector will not generate alarms on any fire panel
which is connected, e.g. for use during detector maintenance. The “Fault” light will be
illuminated on the detector front panel. The isolated condition will be disabled auto-
matically after 7 days if not manually disabled. This function is disabled by default.
3.17 Latching alarms
–
Alarm actions
tab
When this function box is ticked it requires a reset signal to clear an alarm condition.
Reset can be remote (see section 3.14), from the Remote Software (see section 4.1) or
from a Command Module.
If unticked, the alarm signal is extinguished as soon as the alarm condition ends. This
is the factory default setting.